Plan Review Notes For Permit 00060163 |
Permit Number |
00060163 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1) NO HYDRAULIC CALCULATIONS PROVIDED | | WITH FIRE SPRINKLER DRAWINGS ON PAGE | | A8.1.THE FIRE SPRINKLER DRAWING DOES | | NOT INCLUDE LOCATION OF FIRE DEPARTMENT | | CONNECTION OR LOCATION OF FIRE HYDRANTS. | | 2) PLEASE PROVIDE COMPLETE FIRE ALARM | | SYSTEM DRAWINGS AND CUT SHEETS FOR FIRE | | ALARM EQUIPMENT SHOWN ON PLANS. A | | SEPARATE PLAN AND PERMIT ARE REQUIRED. | | 3) PLEASE CHECK THE INTERIOR FINISH | | SCHEDULE ON PAGE A12.2. SINCE THE | | BUILDING IS A MIXED OCCUPANCY, THE MOST | | STRINGENT FLAME SPREAD CRITERIA IS TO | | BE USED. |
|