Plan Review Notes
Plan Review Notes For Permit 00060163
Permit Number 00060163
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001)SUBMIT OCCUPANT LOAD OF STRUCTURE
 BASED ON HABITABLE FLOOR SPACE PER TABLE
 407 0F THE SPC.MINIMUM SANITARY REQS.
 SHALL BE BASED UPON THIS OCCUPANT LOAD.
  
 A HANDICAP STALL W/LAVATORY SHALL BE
 PROVIDED IN THE RESTROOMS PER FACBC
 SECS.4.17.3, 4.22.4.
  
 SHT.A9.1-DETAIL #7-H.C.URINAL SHALL BE
 MOUNTED MAX.17"PER FACBC SEC.4.18.2.
  
 MAX.TEMPERATURE OF WATER TO RESTROOMS
 SHALL BE 110 DEGREES PER F.E.C SEC.
 412.1ABCD.2.3.2.
  
 DRINKING FOUNTAIN AT VOLLEYBALL COURT
 SHALL BE H.C. ACCESSIBLE AND ON AN
 ACCESSIBLE ROUTE PER FACBC SEC.4.3
  
 SUBMIT COMPLETE STORM DRAINAGE ISOMETRIC
 FOR REVIEW.SHOW SLOPE OF PIPE,PIPE SIZES
 AND PROVISIONS FOR SECONDARY(EMERGENCY)
 DRAINAGE.COMPLY W/SPC SEC.1108.1, 1108.2
 1109.1,1109.3 AND APPENDIX "A".
  
 A GREASE TRAP IS REQUIRED ON THE
 SANITARY SYSTEM PER SPC SEC.1004.4.
 CONTACT R.COMPO AT CITY OF W.P.B.
 (561)835-7423.SUBMIT APPROVAL FORM FROM
 UTILITIES FOR GREASE TRAP. SUBMIT DETAIL
 OF GREASE TRAP.
  
 SHT.P3.1-WATER CLOSETS NOT PERMITTED ON
 WET VENTS PER COUNTYWIDE AMENDMENTS TO
 SPC SEC.911.1.1
  
 CIRCUIT AND LOOP SYSTEM SHALL COMPLY W/
 SPC SEC.914.1.
  
 EMERGENCY OVERFLOW IS REQD.ON THE COND.
 DRAIN TO DRYWELL.SPC 701.4,
  
 SUBMIT WATER ISOMETRIC FOR ALL AREAS OF
 NEW WORK.COUNTYWIDE AMENDMENTS TO SPC
 SEC.104.2.1.
  
 A DEP PERMIT IS REQD.FOR THE INSTALL-
 ATION OF THE WATER SYSTEMS.COUNTYWIDE
 AMENDMENTS TO SPC SEC.101.4.7.
  
 CLEARLY SHOW LENGTH AND WIDTH OF TOILET
 ROOMS AND STALLS.COMPLY W/FACBC SECS.
 4.17.3.,4.16.2.