2001-01-08 00:00:00 | 1)SUBMIT OCCUPANT LOAD OF STRUCTURE |
| BASED ON HABITABLE FLOOR SPACE PER TABLE |
| 407 0F THE SPC.MINIMUM SANITARY REQS. |
| SHALL BE BASED UPON THIS OCCUPANT LOAD. |
| |
| A HANDICAP STALL W/LAVATORY SHALL BE |
| PROVIDED IN THE RESTROOMS PER FACBC |
| SECS.4.17.3, 4.22.4. |
| |
| SHT.A9.1-DETAIL #7-H.C.URINAL SHALL BE |
| MOUNTED MAX.17"PER FACBC SEC.4.18.2. |
| |
| MAX.TEMPERATURE OF WATER TO RESTROOMS |
| SHALL BE 110 DEGREES PER F.E.C SEC. |
| 412.1ABCD.2.3.2. |
| |
| DRINKING FOUNTAIN AT VOLLEYBALL COURT |
| SHALL BE H.C. ACCESSIBLE AND ON AN |
| ACCESSIBLE ROUTE PER FACBC SEC.4.3 |
| |
| SUBMIT COMPLETE STORM DRAINAGE ISOMETRIC |
| FOR REVIEW.SHOW SLOPE OF PIPE,PIPE SIZES |
| AND PROVISIONS FOR SECONDARY(EMERGENCY) |
| DRAINAGE.COMPLY W/SPC SEC.1108.1, 1108.2 |
| 1109.1,1109.3 AND APPENDIX "A". |
| |
| A GREASE TRAP IS REQUIRED ON THE |
| SANITARY SYSTEM PER SPC SEC.1004.4. |
| CONTACT R.COMPO AT CITY OF W.P.B. |
| (561)835-7423.SUBMIT APPROVAL FORM FROM |
| UTILITIES FOR GREASE TRAP. SUBMIT DETAIL |
| OF GREASE TRAP. |
| |
| SHT.P3.1-WATER CLOSETS NOT PERMITTED ON |
| WET VENTS PER COUNTYWIDE AMENDMENTS TO |
| SPC SEC.911.1.1 |
| |
| CIRCUIT AND LOOP SYSTEM SHALL COMPLY W/ |
| SPC SEC.914.1. |
| |
| EMERGENCY OVERFLOW IS REQD.ON THE COND. |
| DRAIN TO DRYWELL.SPC 701.4, |
| |
| SUBMIT WATER ISOMETRIC FOR ALL AREAS OF |
| NEW WORK.COUNTYWIDE AMENDMENTS TO SPC |
| SEC.104.2.1. |
| |
| A DEP PERMIT IS REQD.FOR THE INSTALL- |
| ATION OF THE WATER SYSTEMS.COUNTYWIDE |
| AMENDMENTS TO SPC SEC.101.4.7. |
| |
| CLEARLY SHOW LENGTH AND WIDTH OF TOILET |
| ROOMS AND STALLS.COMPLY W/FACBC SECS. |
| 4.17.3.,4.16.2. |