2005-04-11 00:00:00 | ************ UNSAT ************* |
| |
| *** PLEASE SEE ATTACHED NOTES FROM |
| 8/27/04 AND PLEASE SEE NEW NOTES DUE TO |
| MAJOR CHANGES IN PLANS. |
| |
| 1) NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| -ED PER 210.8A-6 |
| |
| 2)NOTE: PLEASE SEE ALL OUTSIDE AND BATH |
| RECEPTS ARE ALSO TO BE GFI/GFI |
| PROTECTED. |
| 210.8 |
| |
| 3)NOTE: PLEASE SEE REVISIONS FOR SERVICE |
| ARE NOW CHANGING FROM THE LAST THREE |
| REVISIONS SUBMITTED?? |
| PLEASE SEE PLANS SHOW A "PANEL C" TO BE |
| FED YET, PLANS AND RISER DO NOT SHOW |
| THIS PANEL? |
| 215.5 |
| |
| 4)NOTE: PLEASE SEE RISER NOW INDICATES A |
| 350A SERVICE, PLEASE SEE 250.66, A MIN |
| OF #2 FOR GROUNDING ELECTRODE CONDUCTOR |
| IS REQUIRED. |
| |
| 5)NOTE: PLEASE SUBMIT COMPLETE PANEL |
| SCHEDULES INCLUDING ALL OCP AND AWG'S |
| FOR ALL BRANCH CIRCUITS. |
| 215.5 |
| |
| 6)NOTE: PLEASE SUBMIT LOAD CALCULATIONS |
| PER NEC 220.31/220.31B |
| |
| 7)NOTE: PLEASE SEE MISSINF RECEPTS PER |
| 210.52E/210.8 |
| |
| 8)NOTE: PLEASE SEE SERVICE CLEARENCES DO |
| NOT MEET 110.26, AS PER CONVERSATION |
| OVER A YEAR AGO, WALL WAS GOING TO BE |
| MOVED TO MEET MIN 110.26, YET PLANS DO |
| NOT CORRELATE WITH THIS CHANGE. |
| |
| 9)NOTE: PLEASE SEE SD'S SHOWN BOTH |
| INSIDE MASTER BEDROOM. |
| PLEASE SEE NFPA-72 8-1.4.1.6.2 |
| |
| 10)NOTE: PLEASE CORRELATE ELECTRICAL |
| LOAD CALCS, PLANS AND MECH PLANS FOR |
| SIZE OF A/C UNITS/ HEAT STRIPS ETC. |
| 215.5 |
| |
| 11)NOTE: PLEASE SEE SEC'S ARE SHOWN AS |
| 2/0'S, PLEASE SEE 310.15B6 FOR MIN |
| SIZING. IF THESE ARE FPL CONDUCTORS, |
| PLEASE DO NOT INDICATE SIZE, (ONLY IF |
| FPL OWNED CONDUCTORS). |
| |
| 12)NOTE: PLEASE CORRELATE REV DATES ON |
| TITLE BLOCK WITH PLANS. PLEASE SEE PLANS |
| INDICATE LAST REVISED DATE OF 4/01 ?? |
| |
| 13)NOTE: PLEASE SEE COPY OF FS |
| 553.80(2)(B) WITH RESPECT TO DESIGN |
| PROFESSIONAL. |
| IF PLANS COME BACK WITH "ANY" OF THE |
| SAME COMMENTS FROM PREVIOUS REVIEWS NOT |
| ADDRESSED, A 4X FEE SHALL BE ACCESSSED |
| TO THE DESIGN PROFESSIONAL. |
| |
| 14)NOTE: PLEASE SEE AS PER PER OUR |
| RECORDS, NO ELECTRICAL ROUGH INSPECTIONS |
| WERE EVER MADE UNDER PREVIOUS OR NEW |
| ELECTRICAL PERMIT. PLEASE SEE 105.6 FBC |
| FOR REQUIRED INSPECTIONS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |