2005-04-11 00:00:00************ UNSAT *************
  
 *** PLEASE SEE ATTACHED NOTES FROM
 8/27/04 AND PLEASE SEE NEW NOTES DUE TO
 MAJOR CHANGES IN PLANS.
  
 1) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 2)NOTE: PLEASE SEE ALL OUTSIDE AND BATH
 RECEPTS ARE ALSO TO BE GFI/GFI
 PROTECTED.
 210.8
  
 3)NOTE: PLEASE SEE REVISIONS FOR SERVICE
 ARE NOW CHANGING FROM THE LAST THREE
 REVISIONS SUBMITTED??
 PLEASE SEE PLANS SHOW A "PANEL C" TO BE
 FED YET, PLANS AND RISER DO NOT SHOW
 THIS PANEL?
 215.5
  
 4)NOTE: PLEASE SEE RISER NOW INDICATES A
 350A SERVICE, PLEASE SEE 250.66, A MIN
 OF #2 FOR GROUNDING ELECTRODE CONDUCTOR
 IS REQUIRED.
  
 5)NOTE: PLEASE SUBMIT COMPLETE PANEL
 SCHEDULES INCLUDING ALL OCP AND AWG'S
 FOR ALL BRANCH CIRCUITS.
 215.5
  
 6)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 PER NEC 220.31/220.31B
  
 7)NOTE: PLEASE SEE MISSINF RECEPTS PER
 210.52E/210.8
  
 8)NOTE: PLEASE SEE SERVICE CLEARENCES DO
 NOT MEET 110.26, AS PER CONVERSATION
 OVER A YEAR AGO, WALL WAS GOING TO BE
 MOVED TO MEET MIN 110.26, YET PLANS DO
 NOT CORRELATE WITH THIS CHANGE.
  
 9)NOTE: PLEASE SEE SD'S SHOWN BOTH
 INSIDE MASTER BEDROOM.
 PLEASE SEE NFPA-72 8-1.4.1.6.2
  
 10)NOTE: PLEASE CORRELATE ELECTRICAL
 LOAD CALCS, PLANS AND MECH PLANS FOR
 SIZE OF A/C UNITS/ HEAT STRIPS ETC.
 215.5
  
 11)NOTE: PLEASE SEE SEC'S ARE SHOWN AS
 2/0'S, PLEASE SEE 310.15B6 FOR MIN
 SIZING. IF THESE ARE FPL CONDUCTORS,
 PLEASE DO NOT INDICATE SIZE, (ONLY IF
 FPL OWNED CONDUCTORS).
  
 12)NOTE: PLEASE CORRELATE REV DATES ON
 TITLE BLOCK WITH PLANS. PLEASE SEE PLANS
 INDICATE LAST REVISED DATE OF 4/01 ??
  
 13)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONAL.
 IF PLANS COME BACK WITH "ANY" OF THE
 SAME COMMENTS FROM PREVIOUS REVIEWS NOT
 ADDRESSED, A 4X FEE SHALL BE ACCESSSED
 TO THE DESIGN PROFESSIONAL.
  
 14)NOTE: PLEASE SEE AS PER PER OUR
 RECORDS, NO ELECTRICAL ROUGH INSPECTIONS
 WERE EVER MADE UNDER PREVIOUS OR NEW
 ELECTRICAL PERMIT. PLEASE SEE 105.6 FBC
 FOR REQUIRED INSPECTIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved