Date Text
2004-08-27 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE AN ADDITION FOR AHU AND
 WH IS NOW BEING SHOWN AS BUILT INFRONT
 OF ELECTRICAL SERVICE W/OUT MEETING
 CLEARENCE REQUIRED PER 110.26
 PLEASE NOTE: THIS ADDITION WILL BE
 REQUIRED MOVED TO MEET 110.26
  
 2)NOTE: PLEASE SEE THERE IS NOW MORE
 A/C SYSTEMS BEING ADDED.
 PLEASE PROVIDE COMPLETE LOAD CALCULATION
 -S FOR SERVICE. PLEASE ALSO PROVIDE
 PANEL SCHEDULES W/ MIN CIRCUITS REQUIRED
 215.5/ 220.31B
  
 3)NOTE: PLEASE SEE 210.8 FOR REQUIRED
 GFI RECETPS FOR OUTSIDE.
 PLEASE ALSO SEE BATHS ETC.
  
 4)NOTE: PLEASE SEE 210.52D FOR MISSING
 REQUIRED RECEPT IN BATH.
  
 PLEASE SEE THAT THE REQUIRED INSPECTIONS
 MUST BE CALLED IN FOR ANY ELECTRICAL
 WORK AND OTHER TRADES ALSO.
 FBC 105.6
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  