Plan Review Notes
Plan Review Notes For Permit 00060130
Permit Number 00060130
Review Stop P
Sequence Number 4
Notes
Date Text
2005-04-15 00:00:00DENIED
 REFERENCE: SBCCI-94 STANDARD PLUMBING
  
 CODE
 SBCCI-97 STANDARD BUILDING
 CODE
  
 1) SHT S-1 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT
 MEET CODE REQUIREMENTS. CORRECT THE
 FOLLOWING:
 A) THE FLOOR DRAINS SHALL HAVE A TRAP
 PER SECTION 409.4.1.2.
 B) WASH MACHINE SHALL NOT DRAIN THROUGH
 THE WET VENT FOR THE BATHROOM FIXTURES.
 SECTION 611.
 C) 3" VENT THROUGH THE TIE BEAM IS NOT
 APPROVED. SECTION 1907.3.6(3). MAXIMUM
 2" INSIDE DIAMETER NOMINAL.
 D) DEAD ENDS NOT APPROVED. SECTION
 311.7.3
 2) FLOOR PLAN SHOWS THE FLOOR DRAIN
 UNDER THE BATH TUB. THE FLOOR DRAIN
 SHALL BE ACCESSIBLE PER SECTION
 409.4.1.2.
 3) SEE ATTACHED SHEET FOR AN EXAMPLE OF
 A SANITARY RISER DIAGRAM THAT REFLECTS
 THE FLOOR PLAN AND MEETS THE CODE
 REQUIREMENTS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]