Plan Review Notes For Permit 00060130 |
Permit Number |
00060130 |
|
Review Stop |
P |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2005-04-15 00:00:00 | DENIED | | REFERENCE: SBCCI-94 STANDARD PLUMBING | | | | CODE | | SBCCI-97 STANDARD BUILDING | | CODE | | | | 1) SHT S-1 SANITARY RISER DIAGRAM DOES | | NOT REFLECT THE FLOOR PLAN, NOR DOES IT | | MEET CODE REQUIREMENTS. CORRECT THE | | FOLLOWING: | | A) THE FLOOR DRAINS SHALL HAVE A TRAP | | PER SECTION 409.4.1.2. | | B) WASH MACHINE SHALL NOT DRAIN THROUGH | | THE WET VENT FOR THE BATHROOM FIXTURES. | | SECTION 611. | | C) 3" VENT THROUGH THE TIE BEAM IS NOT | | APPROVED. SECTION 1907.3.6(3). MAXIMUM | | 2" INSIDE DIAMETER NOMINAL. | | D) DEAD ENDS NOT APPROVED. SECTION | | 311.7.3 | | 2) FLOOR PLAN SHOWS THE FLOOR DRAIN | | UNDER THE BATH TUB. THE FLOOR DRAIN | | SHALL BE ACCESSIBLE PER SECTION | | 409.4.1.2. | | 3) SEE ATTACHED SHEET FOR AN EXAMPLE OF | | A SANITARY RISER DIAGRAM THAT REFLECTS | | THE FLOOR PLAN AND MEETS THE CODE | | REQUIREMENTS. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|