Plan Review Notes For Permit 00060130 |
Permit Number |
00060130 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-03-12 00:00:00 | DENIED; | | | | RISER DIAGRAM NOT TO CODE. HAVE PLUMBING | | CONTRACTOR DRAW PLUMBING RISER AND LINE | | DRAWING SHOWING HOW PLUMBING WILL BE | | INSTALLED.FLOOR DRAINS MUST HAVE TRAP | | PRIMERS, 3" STACK IS WERE W/M IS THAT | | PIPE BY CODE SHOULD HAVE A CLEAN OUT AT | | 48" FROM THE FLOOR. CONTINUEING YOUR | | BUILDING DRAIN DRAIN IS NOT TO CODE. | | | | PLUMBING PLAN REVIEW BY | | JOHN LEECH | | 659-8096 EXT. 8377 |
|