Plan Review Notes
Plan Review Notes For Permit 00060130
Permit Number 00060130
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************** PROVISO *****************
  
 1)NOTE: PLEASE NOTE THAT REQ`MENTS FOR
 SMOKE DETECTORS FOR ENTIRE HOUSE WILL
 NEED TO BE BROUGHT UP TO CODE INSIDE
 AND OUTSIDE ALL SLEEPING ROOMS.
 NFPA-72
  
 2)NOTE: PLEASE NOTE 210-70 FOR EGRESS
 LIGHTING. SWITCHES MUST BE INSTALLED
 FOR EXISTING ROOMS EXITING OUTSIDE.
 SWITCH IS TO BE LOCATED IN EACH ROOM.
  
 3)NOTE;PLEASE SUBMIT PANEL
 SCHEDULES FOR BOTH PANELS.PLEASE INCLUDE
 ALL THE REQ`D CIRCUITS SHOWN.
 PLEASE LIST BATH(S) CIRCUIT(S) 210-11-C-
 -3.
  
 4)NOTE:PLEASE IDENTIFY THE OUTLET AT
 A/C CU LOCATIONS.??
  
 5)NOTE: PLEASE INCLUDE THE BLDG.STEEL
 OF NEW STRUCTURE AS PART OF THE GROUND-
 -ING ELECTRODE SYSTEM. AS REQ`D BY NEC
 ART;250-50. PLEASE SHOW ON RISER
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. PLEASE SUBMIT BEFORE ROUGH
 ELECTRICAL INSPECTION IS CALLED IN.
 FI THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372