Plan Review Notes For Permit 00051555 |
Permit Number |
00051555 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | PRIVATE TOILET(ROOM #523)SHALL BE | | HANDICAP ADAPTABLE PER FACBC SEC.4.1.3. | | (11).PROVIDE DETAILS FOR WOOD BLOCKING | | FOR FUTURE INSTALLATION OF GRAB BARS. | | | | WATER CLOSET SHALL BE 18"FROM FINISH | | WALL TO CENTER OF TOILET PER FACBC FIG. | | 28. | | | | LOCATION OF WATER CLOSET IN TOILET ROOM | | SHALL NOT INTERFERE W/NORMAL OPERATION | | OF DOOR.SPC SEC.404.2. | | | | SINK IN BREAK ROOM SHALL COMPLY W/FACBC | | SEC.4.24.1-4.24.7. | | | | DOOR OPENING TO TOILET ROOM SHALL COMPLY | | W/FACBC SEC.4.13.5. | | | | SUBMIT SQUARE FOOTAGE OF OCCUPIED SPACE. | | NUMBERAND TYPE OF MIN.REQD.SANITARY | | FACILITIES SHALL COMPLY W/SPC TABLE 407. |
|