Plan Review Notes
Plan Review Notes For Permit 00051555
Permit Number 00051555
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PRIVATE TOILET(ROOM #523)SHALL BE
 HANDICAP ADAPTABLE PER FACBC SEC.4.1.3.
 (11).PROVIDE DETAILS FOR WOOD BLOCKING
 FOR FUTURE INSTALLATION OF GRAB BARS.
  
 WATER CLOSET SHALL BE 18"FROM FINISH
 WALL TO CENTER OF TOILET PER FACBC FIG.
 28.
  
 LOCATION OF WATER CLOSET IN TOILET ROOM
 SHALL NOT INTERFERE W/NORMAL OPERATION
 OF DOOR.SPC SEC.404.2.
  
 SINK IN BREAK ROOM SHALL COMPLY W/FACBC
 SEC.4.24.1-4.24.7.
  
 DOOR OPENING TO TOILET ROOM SHALL COMPLY
 W/FACBC SEC.4.13.5.
  
 SUBMIT SQUARE FOOTAGE OF OCCUPIED SPACE.
 NUMBERAND TYPE OF MIN.REQD.SANITARY
 FACILITIES SHALL COMPLY W/SPC TABLE 407.