2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR
 MAINS/PANELS PER 110-9 AND 215-5
  
 2)NOTE: MISSING SD`S INSIDE AND OUTSIDE
 ALL SLEEPING ROOMS. NFPA-72 2-2.1.1.1
 AND ON EACH LEVEL.
  
 3)NOTE: PLEASE LIST THE REQ`D DEDICATED
 BATH(S) CIRCUIT(S) PER 210-11-C-3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 659-8096 EXT 8372