Plan Review Notes For Permit 00051520 |
Permit Number |
00051520 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | *************** UNSAT ***************** | | | | 1)NOTE: PLEASE SUBMIT AIC RATING FOR | | MAIN. MAINS ARE TO BE RATED FOR THE | | AVAILABLE FAULT CURRENT. 110-9 215-5 | | | | 2)NOTE: PLEASE LIST ON PANEL SCHEDULE | | THE REQ`D DEDICATED BATH(S) CIRCUIT(S) | | PER 210-52-C-3/ 215-5 | | | | 3)NOTE:PLEASE NOTE THAT IN YOUR NOTES | | YOU REF.THE 96 NEC. AS OF 3/1/00 WE ARE | | UNDER "99" NEC. | | | | 4)NOTE: PLEASE INCLUDE THE BLDG. STEEL | | ON RISER. IT IS SHOWN BUT PLEASE INK IT | | IN.215-5 | | | | 5)NOTE:PLEASE SEE MISSING OUTLET IN BED- | | -ROOM #4. 210-52 | | | | 6)NOTE:PLEASE SHOW ALL OUTLETS SERVING | | KITCHEN COUNTESPACE AS GFI/GFIPROTECT- | | -ED. 210-8-A-6 | | | | 7)NOTE: SMOKE DETECTOR REQ`D IN COMMON | | AREA ON FIRST LEVEL IN MULTI-LEVEL DWELL | | -ING. NFPA-72 | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL 659-8096 EXT 8372 |
|