2001-01-08 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT AIC RATING FOR
 MAIN. MAINS ARE TO BE RATED FOR THE
 AVAILABLE FAULT CURRENT. 110-9 215-5
  
 2)NOTE: PLEASE LIST ON PANEL SCHEDULE
 THE REQ`D DEDICATED BATH(S) CIRCUIT(S)
 PER 210-52-C-3/ 215-5
  
 3)NOTE:PLEASE NOTE THAT IN YOUR NOTES
 YOU REF.THE 96 NEC. AS OF 3/1/00 WE ARE
 UNDER "99" NEC.
  
 4)NOTE: PLEASE INCLUDE THE BLDG. STEEL
 ON RISER. IT IS SHOWN BUT PLEASE INK IT
 IN.215-5
  
 5)NOTE:PLEASE SEE MISSING OUTLET IN BED-
 -ROOM #4. 210-52
  
 6)NOTE:PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTESPACE AS GFI/GFIPROTECT-
 -ED. 210-8-A-6
  
 7)NOTE: SMOKE DETECTOR REQ`D IN COMMON
 AREA ON FIRST LEVEL IN MULTI-LEVEL DWELL
 -ING. NFPA-72
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372