Plan Review Notes For Permit 00051311 |
Permit Number |
00051311 |
|
Review Stop |
P |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2001-09-27 00:00:00 | DENIED | | REFERENCE: SPC-94 | | | | PAGE P6-1 WATER HAMMER ARRESTORS TO BE | | INSTALLED PER MANUFACTURE INSTALLATION | | INSTRUCTIONS AND WH-PDI 201 AND NOT AT | | THE TOP OF THE DROPS AS SHOWN ON DOMES- | | TIC WATER ISOMETRIC. PLEASE SHOW PROPER | | LOCATION ON PLANS. | | | | REVIEW BY KEN STEVENS | | (561) 659-8096 EXT. 8377 |
|