Plan Review Notes
Plan Review Notes For Permit 00051311
Permit Number 00051311
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001)SITE PLAN-SHT.5-WATER SERVICE IS SHOWN
 AS 2 1/2" INCH AND ALSO AS 3".CLARIFY.
  
 2)PLEASE NOTE THE OCCUPANT LOAD ON THE
 PLANS PER SPC TABLE 407.SEE SPC SEC.
 407.1.3.FOR ALLOWED DEDUCTIBLE AREAS.
 SHOW THE CALCULATIONS ON THE PLAN.
  
 3)SHT.A-4-IDENTIFY THE HANDICAP URINAL
 ON THE PLANS.THE STALL DOOR CANNOT
 SWING INTO THE CLEAR FLOOR SPACE FOR THE
 URINAL PER FACBC SEC.4.17.5.
  
 4)SHT.A-8-PLEASE CLARIFY SECONDARY
 DRAINAGE CALCULATIONS.SEE APPENDIX "A"
 IN THE SPC FOR SCUPPER SIZING.
  
 5)DELETE REFERENCE TO SFBC AT SAND/OIL
 INTERCEPTOR.SHT.P0-1.
  
 6)SHT.P5-1-MAX.NUMBER OF FIXTURE UNITS
 ON 3" HORIZONTAL BRANCH CONNECTED TO THE
 BUILDING DRAIN SHALL NOT EXCEED 20 F.U'S
 PER TABLE 714.1.(SEE U/G BRANCH FOR LAV.
 WASTE STACKS.)
  
 7)THE SQ.FOOTAGE DRAINED BY THE ROOF
 DRAINS SHOWN ON SHT.P2.1 DOESN'T
 CORRELATE W/SHT.P5-1.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.