Plan Review Notes For Permit 00051311 |
Permit Number |
00051311 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1)SITE PLAN-SHT.5-WATER SERVICE IS SHOWN | | AS 2 1/2" INCH AND ALSO AS 3".CLARIFY. | | | | 2)PLEASE NOTE THE OCCUPANT LOAD ON THE | | PLANS PER SPC TABLE 407.SEE SPC SEC. | | 407.1.3.FOR ALLOWED DEDUCTIBLE AREAS. | | SHOW THE CALCULATIONS ON THE PLAN. | | | | 3)SHT.A-4-IDENTIFY THE HANDICAP URINAL | | ON THE PLANS.THE STALL DOOR CANNOT | | SWING INTO THE CLEAR FLOOR SPACE FOR THE | | URINAL PER FACBC SEC.4.17.5. | | | | 4)SHT.A-8-PLEASE CLARIFY SECONDARY | | DRAINAGE CALCULATIONS.SEE APPENDIX "A" | | IN THE SPC FOR SCUPPER SIZING. | | | | 5)DELETE REFERENCE TO SFBC AT SAND/OIL | | INTERCEPTOR.SHT.P0-1. | | | | 6)SHT.P5-1-MAX.NUMBER OF FIXTURE UNITS | | ON 3" HORIZONTAL BRANCH CONNECTED TO THE | | BUILDING DRAIN SHALL NOT EXCEED 20 F.U'S | | PER TABLE 714.1.(SEE U/G BRANCH FOR LAV. | | WASTE STACKS.) | | | | 7)THE SQ.FOOTAGE DRAINED BY THE ROOF | | DRAINS SHOWN ON SHT.P2.1 DOESN'T | | CORRELATE W/SHT.P5-1. | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | QUESTIONS. | | TIMOTHY LARGE | | PLUMBING PLANS EXAMINER. |
|