Date |
Text |
2001-01-08 00:00:00 | 1) BUILDING ADDRESS NOT SHOWN ON |
| ELEVATION DRAWINGS. BUILDING ADDRESSES |
| TO COMPLY WITH CITY CODE REQUIREMENTS. |
| 2) PLEASE CONTACT THE FIRE PREVENTION |
| BUREAU AT 835-2910 TO REQUEST KNOX-BOX |
| APPLICATION(S) FOR THE BUILDINGS. |
| 3) ELEVATORS TO COMPLY WITH ANSI A17.1 |
| AND THE UNIFORM FIRE CODE FOR ELEVATORS |
| 4A-47. |
| 4) INTERIOR FINISHES IN EXITS TO BE |
| CLASS A OR B. INTERIOR FINISHES IN |
| OFFICES TO BE CLASS A, B, OR C. |
| 5) PLEASE PROVIDE FIRE ALARM SYSTEM SHOP |
| DRAWINGS FOR FIRE ALARM EQUIPMENT SHOWN |
| ON DRAWINGS. CUT SHEETS REQUIRED ON |
| ALL DEVICES PLANNED FOR USE. |
| 6) FIRE ALARM SYSTEM AND FIRE SPRINKLER |
| SYSTEM TO BE MONITORED BY A UL LISTED |
| CENTRAL STATION APPROVED BY THE FIRE |
| RESCUE DEPARTMENT. |
| 7) EXIT DOORS 113 AND 116 WHEN OPENED |
| ARE NOT TO INTERFERE WITH ONE ANOTHER. |
| 8) EXIT DOORS WHEN OPENED ARE NOT TO |
| PROJECT MORE THAN SEVEN INCHES INTO |
| A REQUIRED EXIT CORRIDOR. |
| 9) ALL STAIRS TO COMPLY WITH NEW STAIRS |
| PER NFPA 101, THE LIFE SAFETY CODE, |
| 1985 EDITION. |
| APPROVED PROVISO: |