Plan Review Notes
Plan Review Notes For Permit 00051311
Permit Number 00051311
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESSES
 TO COMPLY WITH CITY CODE REQUIREMENTS.
 2) PLEASE CONTACT THE FIRE PREVENTION
 BUREAU AT 835-2910 TO REQUEST KNOX-BOX
 APPLICATION(S) FOR THE BUILDINGS.
 3) ELEVATORS TO COMPLY WITH ANSI A17.1
 AND THE UNIFORM FIRE CODE FOR ELEVATORS
 4A-47.
 4) INTERIOR FINISHES IN EXITS TO BE
 CLASS A OR B. INTERIOR FINISHES IN
 OFFICES TO BE CLASS A, B, OR C.
 5) PLEASE PROVIDE FIRE ALARM SYSTEM SHOP
 DRAWINGS FOR FIRE ALARM EQUIPMENT SHOWN
 ON DRAWINGS. CUT SHEETS REQUIRED ON
 ALL DEVICES PLANNED FOR USE.
 6) FIRE ALARM SYSTEM AND FIRE SPRINKLER
 SYSTEM TO BE MONITORED BY A UL LISTED
 CENTRAL STATION APPROVED BY THE FIRE
 RESCUE DEPARTMENT.
 7) EXIT DOORS 113 AND 116 WHEN OPENED
 ARE NOT TO INTERFERE WITH ONE ANOTHER.
 8) EXIT DOORS WHEN OPENED ARE NOT TO
 PROJECT MORE THAN SEVEN INCHES INTO
 A REQUIRED EXIT CORRIDOR.
 9) ALL STAIRS TO COMPLY WITH NEW STAIRS
 PER NFPA 101, THE LIFE SAFETY CODE,
 1985 EDITION.
 APPROVED PROVISO: