2001-01-08 00:00:00MAX.OF 5350 SQ.FT.IS PERMITTED TO DRAIN
 INTO 6" PIPE AT 1/8" PER FT.SLOPE.SEE
 SPC TABLE 1108.2.REVISE PIPE SIZE FOR
 RW.
  
 SHT.P1.01-NOTE #3-TESTING OF WATER
 SUPPLY SYSTEM SHALL COMPLY W/SPC SEC.
 311.3.
  
 DESIGN OF OVERFLOW DRAINAGE SYSTEM SHALL
 COMPLY W/SPC SEC.1109.1-1109.3 AND
 APPENDIX "A" OF SPC.
  