Plan Review Notes For Permit 00051297 |
Permit Number |
00051297 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | MAX.OF 5350 SQ.FT.IS PERMITTED TO DRAIN | | INTO 6" PIPE AT 1/8" PER FT.SLOPE.SEE | | SPC TABLE 1108.2.REVISE PIPE SIZE FOR | | RW. | | | | SHT.P1.01-NOTE #3-TESTING OF WATER | | SUPPLY SYSTEM SHALL COMPLY W/SPC SEC. | | 311.3. | | | | DESIGN OF OVERFLOW DRAINAGE SYSTEM SHALL | | COMPLY W/SPC SEC.1109.1-1109.3 AND | | APPENDIX "A" OF SPC. | | | | I CAN BE REACHED AT 561-659-8096,EXT. | | 8377 IF YOU HAVE ANY QUESTIONS. | | TIMOTHY LARGE,PLUMBING PLANS EXAMINER. |
|