Plan Review Notes
Plan Review Notes For Permit 00051297
Permit Number 00051297
Review Stop B
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001. ENGINEER TO PROVIDE LETTER INDICATING
 1/4" ROOF SLOPE AS PER CODE. OK 6/6/00
 2. ROOFING SYSTEM SHALL MEET THE
 REQUIREMENTS OF APPENDIX F FOR FIRST
 FIRE DISTRICT.OK 6/6/00
 3. FLORIDA ENERGY SHEETS REQUIRED.OK 6/6
 4. SHEET S-3 MEZZANINE DESIGNED FOR
 50PSF. PLANS SHOW THAT THE AREA IS TO BE
 USED FOR PUBLIC SEATING THUS 100PSF
 REQUIRED SEE TABLE 1604.1, 1997 SBC.OK6/
 5. SHEET A-1 WINDOWS AND DOORS SUBMIT
 INFORMATION CERTIFYING CODE COMPLIANCE
 TO 1997 SBC, SECTION 1006.2.4, 3/4 HOUR
 FIRE RATING.OK 6/6/00
 6. ALL EXTER GLAZING, SUBMIT PRODUCT
 APPROVAL INFORMATION FOR LARGE MISSLE
 IMPACT. SBCCI OR DADE COUNTY.OK 6/6/00
 7. SIGNS AND AWNINGS REQUIRE SEPERATE
 PERMITS.
 8. NO INTERIOR WORK IS COVERED BY THIS
 PERMIT.
  
 INFORMATION CONTACT JOHN STANDBERG AT
 561-988-4002.