2001-01-08 00:00:00 | CHECKLIST: |
| 1-CONNECTORS SPECIFIED ON NEW DRAWINGS |
| BY TURQUOISE, INC ARE NOT CORRECT. |
| CHECK SEMCO CATALOGUE AND SPECIFY |
| PROPER CONNECTORS. SEE PLANS FOR |
| COMMENTS. |
| 2-SECTION A-A SHOWS CONNECTORS FOR |
| RAFTERS AT FLAT ROOF ONLY. |
| SPECIFY CONNECTORS FOR NEW TRUSSES. |
| 3-SPECIFY HOW IS CROSS VENTILATION FOR |
| NEW ATTIC ACHIEVED. |
| SEE SECTION 2309.7 SBC 1997. |
| 4-CONNECTORS SPECIFIED FOR ROOF TRUSSES |
| DON'T HAVE ANY ENGINEERED VALUE FOR |
| LATERAL FORCES. SEE ANCHOR CATALOGUE |
| AND ENGINEERED TRUSS. |
| SPECIFY ANCHOR WITH VALUES FOR UPLIFT |
| AND LATERAL FORCES AS REQUIRED. |
| 5-SPECIFY ANCHORING OF GABLE END TRUSS. |
| SEE ENGINEERED TRUSS. |
| 6-ROOF TRUSSES: |
| -THERE ARE 2 DIFFERENT TRUSS COMPANIES. |
| DECIDE WHICH ONE IS GOING TO BE USED. |
| -TRUSS DRAWINGS TO BE UPDATED & CLEARLY |
| SPECIFY IF USING ASCE 7-95 FOR 145 MPH |
| WIND LOAD OR SBC 1997 FOR 110 MPH WIND |
| LOAD. |
| -TRUSS LAYOUT AND ENGINEERED TRUSSES TO |
| BE SIGNED, SEALED AND DATED AND WITH |
| INFORMATION REQUIRED BY CHAPTER 471 OF |
| FLORIDA STATUTES WHEN SUBMITTING |
| DOCUMENTS FOR PUBLIC RECORDS. |
| -PROFESSIONAL OF RECORD TO REVIEW ALL |
| TRUSS DRAWINGS PRIOR TO SUBMITTAL TO |
| THIS OFFICE. |
| 7-PROVIDE PRODUCT APPROVALS FOR: |
| -OUTSWING FRENCH DOORS. |
| -OUTSWING DOOR AT KITCHEN. |
| -INSWING DOOR AT BATH. |
| -SINGLE HUNG WINDOW. |
| -FLAT ROOF SYSTEM. |
| -SHINGLES. |
| 8-STORM PANELS: |
| -PROVIDE PRODUCT APPROVAL. |
| -PROVIDE A COMPLETE INSTALLATION |
| SCHEDULE AS PER CITY SAMPLE ATTACHED |
| AND A KEY PLAN. |
| -CLEARLY INDICATE ON STORM PANELS DWGS |
| THE MOUNTING METHOD AND ANCHOR AND |
| SPACING TO BE USED ACCORDINT TO THE |
| STRUCTURE TO BE ATTACHED TO. |
| 9-SEE ADDITIONAL COMMENTS ON PLANS, |
| INCLUDING COMMENTS BY THE OTHER TRADES |
| 10-CONTRACTOR NEEDS TO UPDATE LICENSE. |
| |
| |
| |
| |
| NOTES: |
| |
| 1-SEPARATE PERMITS AND FEES WILL BE |
| REQUIRED FOR MECHANICAL, ELECTRICAL, |
| PLUMBING AND ROOFING. |
| 2-RETURN REVIEWED SET AFTER CORRECTIONS |
| ARE DONE TO ORIGINAL DRAWING IN ORDER |
| TO EXPEDITE THE REVIEW PROCESS. |
| 3-IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ AT 659-8096 EXT. 8232. |