Plan Review Notes
Plan Review Notes For Permit 00051136
Permit Number 00051136
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE SUBMIT THE AIC RATING FOR
 NEW MAIN. MAINS MUST BE RATED FOR THE
 AVAILABLE FAULT CURRENT.110-9/215-5
  
  
  
  
  
 3)NOTE: MUST BOND COLD WATER AT ADDITION
 PER 250-50 PLEASE SHOW ON RISER DIAGRAM.
  
 4)NOTE: PLEASE SHOW LOAD CALCULATIONS
 FOR SERVICE. ALL CONTINUOUS LOADS AT
 125%(LIGHTING) ETC. PLEASE SHOW LOAD
 FOR TRACK LIGHTING PER 220-12B, SQ FT
 PER 220.
  
 5)NOTE;PER 250-50 BLDG STEEL MUST BE
 BONDED AT ADDITION.
  
 6)NOTE:PLEASE PROVIDE DISTANCE FROM
 MAIN TO PANEL 'B' IN ADDITION. LENGTH
 OF CONDUCTORS.
  
 PLEASE SUBMIT ALL THE ABOVE INFOMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372