Plan Review Notes For Permit 00051132 |
Permit Number |
00051132 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ***************** UNSAT **************** | | | | 1)NOTE: AS REQUESTED ON FIRST SET OF | | NOTES. PLEASE SUBMIT AIC RATINGS OF | | MAINS AND PANELS. THIS IS REQ`D BEFORE | | PLANS ARE ISSUED FOR PERMIT. | | MAINS AND PANELS MUST BE RATED FOR THE | | AVAILABLE FAULT CURRENT. FAULT CURRENT | | CALCULATIONS MAY BE SUBMITTED INSTEAD | | OF RATINGS AND CONTRACTOR WILL BE | | RESPONSIBLE FOR INSTALLING EQUIPMENT | | RATED FOR AVAILABLE FAULT GIVEN BY | | CALCULATIONS.THIS REQ`D BY 110-9 AND | | 215-5 OF THE NEC. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL 561-659-8096 EXT 8372 | | | | DEWEY PALMER | | ELETRICAL PLAN REVIEW. |
|