Plan Review Notes For Permit 00051132 |
Permit Number |
00051132 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | A DRINKING FOUNTAIN IS REQD.PER SPC | | TABLE 407.DRINKING FOUNTAIN SHALL COMPLY | | W/FACBC SEC.4.1.3.(10)(A).PROVISIONS | | SHALL BE MADE FOR PEOPLE WHO HAVE | | TROUBLE BENDING OR STOOPING. | | | | WATER HEATER SHALL BE READILY ACCESSIBLE | | PER SPC SEC.501.7.SUPPLY FIXED LADDER | | FOR ACCESSIBILITY OR RELOCATE EWH TO | | FLOOR. | | | | TOILET PAPER DISPENSER SHALL BE A MIN.OF | | 19" TO CENTER PER FACBC SEC.4.16.6 | | | | A CLEAR FLOOR SPACE OF 30"WIDE X 48"DEEP | | SHALL BE PROVIDED AT DRINKING FOUNTAIN | | TO ALLOW A FORWARD APPROACH PER FACBC | | SEC.4.15.5. | | | | DRINKING FOUNTAIN SHALL COMPLY W/FACBC | | SECS.4.15.2.,4.15.3. |
|