Plan Review Notes
Plan Review Notes For Permit 00051132
Permit Number 00051132
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00A DRINKING FOUNTAIN IS REQD.PER SPC
 TABLE 407.DRINKING FOUNTAIN SHALL COMPLY
 W/FACBC SEC.4.1.3.(10)(A).PROVISIONS
 SHALL BE MADE FOR PEOPLE WHO HAVE
 TROUBLE BENDING OR STOOPING.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7.SUPPLY FIXED LADDER
 FOR ACCESSIBILITY OR RELOCATE EWH TO
 FLOOR.
  
 TOILET PAPER DISPENSER SHALL BE A MIN.OF
 19" TO CENTER PER FACBC SEC.4.16.6
  
 A CLEAR FLOOR SPACE OF 30"WIDE X 48"DEEP
 SHALL BE PROVIDED AT DRINKING FOUNTAIN
 TO ALLOW A FORWARD APPROACH PER FACBC
 SEC.4.15.5.
  
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SECS.4.15.2.,4.15.3.