2001-01-08 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE PROVIDE AIC RATINGS OF
 ANY EQUIPMENT BEING INSTALLED. MAINS
 MUST BE RATED FOR THE AVAILABLE FAULT
 CURRENT. 110-9/215-5
  
 2)NOTE:PLEASE NOTE THE OUTLETS REQ`D FOR
 SHOW WINDOWS AS PER 210-62
  
 3)NOTE:PLEASE NOTE AS PER PALM BEACH
 COUNTY/CITY OF WEST PALM BEACH LOCAL
 AMENDMENTS. OUTLET SPACINGTO MEET
 210-50. EVERY 20` OF UNENCUMBERED WALL
 SPACE REGARDLESS OF WALL FIXTURES AND/OR
 OTHER WALL MODIFICATIONS.
  
  
 PLEASE MAKE THE ABOVECHANGES AND
 SUBMIT FOR REVIEW. IF THERE ARE ANY
 QUESTIONS PLEASE CALL 659-8096 EXT 8372