Plan Review Notes For Permit 00051092
Permit Number 00051092
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT APPLICABLE SIZING CHART USED TO
 SIZE THE SYSTEM.SGC SEC.305.4.
  
 SUBMIT EHD NUMBER OF CSST TUBING FOR
 EACH SIZE BEING INSTALLED.SGC SEC.305.4.
  
 SHOW PIPE CONNECTION TO METER,PIPE SIZE
 AND MATERIAL.
  
 SHOW DISTANCE TO MOST REMOTE OUTLET.
 SYSTEM SHALL BE SIZED TO COMPLY W/SGC
 305.4.
  
 SUBMIT DELIVERY PRESSURE TO SYSTEM.SGC
 SEC.305.4.