2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE "AO". NEED TO PROVIDE AN
 ELEVATION CERTIFICATE.
 2-ENERGY CALCULATIONS:
 -REVISE CEILING AREA AS REQUIRED PER
 SECTION 604.1.A.1 OF FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION, 1997 EDITION.
 3-SEE COMMENTS ON PLANS REVISE/UPDATE
 AS REQUIRED FOR FUTURE SUBMITTALS.
 4-COMPLETELY SPECIFY CEILING CONSTRUCT'N
 AT FRONT AND BACK PORCHES. INCLUDING
 FASTENERS TYPE AND SPACING. SECTION
 2504 SBC 1997.
 5-PROVIDE COMPLETE AND LEGIBLE PRODUCT
 APPROVALS FOR: GLASS BLOCK, SLIDING
 GLASS DOORS, ENTRY DOOR AND CIRCLE TOP
 WINDOWS.
 6-STORM PANELS:
 -PROVIDE INSTALLATION SCHEDULE. PLEASE,
 USE CITY SAMPLE AND FILL IN ALL THE
 INFORMATION AS SHOWN ON SAMPLE TO
 ASSURE PROPER INSTALLATION.
 -MARK ANCHOR INSTALLATION SCHEDULE
 ACCORDING TO THE MEAN ROOF HEIGHT,
 DESIGN PRESSURES, EDGE DISTANCE, STORM
 SPAN, CONNECTION TYPE AND STRUCTURE TO
 BE ATTACHED TO.
 NOTE: BE AWARE THAT WINDOW SILLS ARE
 BE AWARE THAT WINDOW SILLS ARE MASONRY
 UNITS. THEREFORE, STRUCTURE TO RECEIVE
 STORM PANELS IS CONCRETE BLOCK NOT
 3,000 PSI CONCRETE.
 7-PROVIDE SOIL TEST REPORT AS PER SEC.
 1804.2.7 OF CITY AMENDMENTS.
 8-FOR FUTURE SUBMITTALS, PLEASE CLEARLY
 INDICATE THE STRUCTURAL DETAILS THAT
 ARE RELATED TO THE SPECIFIC HOUSE AND
 THE OPTION THAT IS GOING TO BE BUILT
 IN ORDER TO EXPEDITE THE REVIEW
 PROCESS.