Date Text
2001-01-08 00:00:001)DRINKING FOUNTAINS SHALL COMPLY W/
 FACBC SEC.4.1.3.(10)(A).PROVISIONS SHALL
 BE MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING AND STOOPING.
  
 2)PAN DRAINS ARE REQUIRED FOR THE HEATER
 PANS.TERMINATION OF DRAINS SHALL
 COMPLY W/SPC SEC.507.8.3.MIN.SIZE OF PAN
 DRAIN SHALL BE MIN.1".SPC 507.8.2.
  
 3)AN ADDITIONAL LAVATORY IS REQD.IN THE
 WOMEN'S TOILET ROOM PER SPC TABLE 407.
 SEE SPACES #1,#7.
  
 4)A MIN.OF 29" IS REQD.UNDER THE H.C.
 LAVS.FACBC SEC.4.19.2.SEE SHT.TI-A3.
  
 5)WATER CLOSETS AND LAVS.IN UNITS #4 & 5
 ARE NOT PROPERLY VENTED.SPC SEC.901.2,
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.