Plan Review Notes For Permit 00050848 |
Permit Number |
00050848 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1)DRINKING FOUNTAINS SHALL COMPLY WITH | | FACBC SEC.4.1.3.(10)(A).PROVISIONS SHALL | | BE MADE FOR PEOPLE WHO HAVE TROUBLE | | BENDING OR STOOPING. | | | | 2)WATER HEATERS CANNOT BE LOCATED IN | | CLEAR FLOOR SPACE FOR WATER CLOSET. | | FACBC SEC.4.2.3.,FIG.#28. | | | | 3)AN ADDITIONAL LAVATORY IS REQD.IN THE | | WOMEN'S TOILET ROOM PER SPC TABLE 407. | | SEE SPACES #1,7. | | | | 4)A MIN.OF 29"IS REQD.UNDER H.C.LAV.PER | | FACBC SEC.4.19.2. | | | | 5)SPACES #4 & 5-WATER CLOSETS,DRINKING | | FOUNTAINS AND LAVATORIES NOT PROPERLY | | VENTED.COMPLY W/SPC SEC.901.2,913.1, | | 913.1.2.& SPC TABLE 714.2. | | | | 6)TOILET ROOM IN SPACE #7 NOT SHOWN ON | | SANITARY RISER.COUNTYWIDE AMENDMENTS TO | | SPC SEC.104.2.1. | | | | 7)NOT MORE THAN 2 FIXTURES SHALL BE | | SUPPLIED BY 1/2" C.W.PER COUNTYWIDE | | AMENDMENTS TO SPC SEC.607.7.MIN.SUPPLY | | TO EWH SHALL BE 3/4".SHOW DRINKING | | FOUNTAINS ON WATER RISERS. | | | | 8)WATER HEATERS SHALL BE EQUIPPED W/HEAT | | TRAPS PER FLA.ENERGY CODE. | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | ANY QUESTIONS. | | | | TIMOTHY LARGE | | PLUMBING PLANS EXAMINER. |
|