Plan Review Notes
Plan Review Notes For Permit 00050848
Permit Number 00050848
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001)DRINKING FOUNTAINS SHALL COMPLY WITH
 FACBC SEC.4.1.3.(10)(A).PROVISIONS SHALL
 BE MADE FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.
  
 2)WATER HEATERS CANNOT BE LOCATED IN
 CLEAR FLOOR SPACE FOR WATER CLOSET.
 FACBC SEC.4.2.3.,FIG.#28.
  
 3)AN ADDITIONAL LAVATORY IS REQD.IN THE
 WOMEN'S TOILET ROOM PER SPC TABLE 407.
 SEE SPACES #1,7.
  
 4)A MIN.OF 29"IS REQD.UNDER H.C.LAV.PER
 FACBC SEC.4.19.2.
  
 5)SPACES #4 & 5-WATER CLOSETS,DRINKING
 FOUNTAINS AND LAVATORIES NOT PROPERLY
 VENTED.COMPLY W/SPC SEC.901.2,913.1,
 913.1.2.& SPC TABLE 714.2.
  
 6)TOILET ROOM IN SPACE #7 NOT SHOWN ON
 SANITARY RISER.COUNTYWIDE AMENDMENTS TO
 SPC SEC.104.2.1.
  
 7)NOT MORE THAN 2 FIXTURES SHALL BE
 SUPPLIED BY 1/2" C.W.PER COUNTYWIDE
 AMENDMENTS TO SPC SEC.607.7.MIN.SUPPLY
 TO EWH SHALL BE 3/4".SHOW DRINKING
 FOUNTAINS ON WATER RISERS.
  
 8)WATER HEATERS SHALL BE EQUIPPED W/HEAT
 TRAPS PER FLA.ENERGY CODE.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 ANY QUESTIONS.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.