Plan Review Notes
Plan Review Notes For Permit 00050848
Permit Number 00050848
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00****************************************
  
 1)NOTE: PLEASE NOTE THAT THE EXTERIOR
 LIGHTING ON BLDG. 'B' CAN NOT BE FED
 FROM THE HOUSE PANEL ON BLDG. "A"
 THE IS A SEPARATE BLDGAND MAY NOT
 HAVE POWER FROM OTHER SERVICE. IF A FIRE
 IN BLDG. "B" OCCURRED AND FIRE DEPT WAS
 TO TURN POWER OFF FOR BLDG"B". THE LIGHT
 -S WOULD STILL BE HOT.
 A SEPARATE HOUSE PANEL MAY BE INSTALLED
 AT BLDG."B".
  
 PLEASE ADDRESS THE ABOVE NOTES AND SUB-
 -MIT FOR REVIEW. THE PLANS WOULD HAVE
 PASSED WITH A PROVISO BUT WERE COMING
 BACK FOR PLUMB NOTES.
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 CITY OF WEST PALM BEACH
 659-8096 EXT8372