Plan Review Notes For Permit 00050848 |
Permit Number |
00050848 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | PLUMBING PLAN REVIEW DENIED | | (1)TENANT SPACES#1,#2 COMPLY WITH SPC-94 | | TAB 407 & SEC 407.1.3,FOOT NOTE 6. | | SEPERATE MALE,FEMALE FACILITIES REQIIRED | | (2) ISOMETRIC OF HOT & COLD WATER PIPING | | LOCATION OF ALL WATER HEATERS. SEC 104.2 | | (3) SHOW LOCATION OF BACK FLOW PREVENTER | | SEC 104.2 | | (4) WATER SUPPLY CONTROL TO EACH TENANT | | SPACE SHALL HAVE A SEPERATE SHUT OFF. | | SEC 610. | | (5) DRINKING FOUNTAINS REQUIRED IN EACH | | UNIT,TAB 407. | | END OF COMMENTS |
|