Plan Review Notes For Permit 00050848 |
Permit Number |
00050848 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | DENIED********************************** | | 1. NEEDS MORE INFO ON A/C UNITS. | | 2. DUCTS, GRILLES, CFM VALUE, TYPE OF | | DUCT AND SIZES. | | 3. INDICATE SMOKE DETECTOR IN THE RETURN | | AIR DUCT IF REQUIRED. | | 4. EXHAUST FANS REQUIRED IN BATHROOM & | | SHOW THE SIZE AND MODEL INFO. | | 5. SHOW CONDENSATE LINES TO THE OUTSIDE. | | 6. RETURN AIR GRILLE & SIZE TO BE SHOWN. |
|