2001-01-08 00:00:00TRUSS DRAWINGS CHECKLIST:
 1-MEAN ROOF HEIGHT IS INCORRECT. THIS IS
 A TWO STORY BUILDING. ARCHITECT'S
 DESIGN CERTIFICATION FOR BUILDING CODE
 COMPLIANCE FORM STATES THAT THE MEAN
 ROOF HEIGHT FOR THIS BUILDING IS 25'-8
  
 NOTE: THERE IS ONLY ONE MEAN ROOF
 HEIGHT FOR ENTIRE BUILDING. SEE TABLE
 1606.2A SBC 1997.
  
 2-REVISE ANCHOR SCHEDULE AS REQUIRED TO
 RESIST THE LOADS AS CALCULATED IN THE
 ENGINEERED TRUSS GT2.
  
 3-TRUSS ENGINEERING LAYOUT IS SLIGHTLY
 DIFFERENT AT BACK OF BUILDING AND
 AT SECOND FLOOR ROOF FRAMING. REVISE
 ARCHITECTURAL ROOF FRAMING PLAN OR
 TRUSS LAYOUT TO MATCH AND SPECIFY THE
 CORRESPONDING CONNECTORS.
  
 4-SPECIFY CONNECTORS FOR TRUSS S1D AND
 FG2D. SEE ENGINEERED TRUSSES.
  
 5-SEE TRUSS LAYOUT FOR ADDITIONAL
 COMMENTS.
  