Plan Review Notes For Permit 00050809 |
Permit Number |
00050809 |
|
Review Stop |
R |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | TRUSS DRAWINGS CHECKLIST: | | 1-MEAN ROOF HEIGHT IS INCORRECT. THIS IS | | A TWO STORY BUILDING. ARCHITECT'S | | DESIGN CERTIFICATION FOR BUILDING CODE | | COMPLIANCE FORM STATES THAT THE MEAN | | ROOF HEIGHT FOR THIS BUILDING IS 25'-8 | | | | NOTE: THERE IS ONLY ONE MEAN ROOF | | HEIGHT FOR ENTIRE BUILDING. SEE TABLE | | 1606.2A SBC 1997. | | | | 2-REVISE ANCHOR SCHEDULE AS REQUIRED TO | | RESIST THE LOADS AS CALCULATED IN THE | | ENGINEERED TRUSS GT2. | | | | 3-TRUSS ENGINEERING LAYOUT IS SLIGHTLY | | DIFFERENT AT BACK OF BUILDING AND | | AT SECOND FLOOR ROOF FRAMING. REVISE | | ARCHITECTURAL ROOF FRAMING PLAN OR | | TRUSS LAYOUT TO MATCH AND SPECIFY THE | | CORRESPONDING CONNECTORS. | | | | 4-SPECIFY CONNECTORS FOR TRUSS S1D AND | | FG2D. SEE ENGINEERED TRUSSES. | | | | 5-SEE TRUSS LAYOUT FOR ADDITIONAL | | COMMENTS. | | | | NOTE: | | -IF YOU HAVE ANY QUESTIONS PLEASE FEEL | | FREE TO CONTACT JULIO GOMEZ AT | | 659-8096 EXT. 8232. |
|