Plan Review Notes
Plan Review Notes For Permit 00050809
Permit Number 00050809
Review Stop R
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00SECOND CHECKLIST:
 1-PERCENTAGE OF OPENINGS ALLOWED BY
 TABLE 600 OF SBC 1997 ISEXCEEDED AT
 RIGHT ELEVATION. DWGS WERE NOT REVISED
 2-DETAIL/SECTION AT COLUMN C8 IS
 INCOMPLETE. IT DOESN'T SPECIFY BOTTOM
 PLATE AND ANCHORS.
 SECTION 104.2.2 CITY AMENDMENTS.
 3-PROVIDE A COMPLETE WALL SECTION AT TWO
 STORY CBS WALL. INCLUDE DETAIL/SPECS
 OF HOW IS SECOND FLOOR FRAMING
 ANCHORED TO THIS WALL. SECTION 104.2.2
 CITY AMENDMENTS TO SBC 1997.
 4-PROVIDE SAFETY GLASS AT BEDROOM #4.
 SECTION 2405.2 SBC 1997.
 5-STAIRS SECTION/DETAIL:
 -NOT ENOUGH INFORMATION IS GIVEN TO
 DETERMINE THE STAIRWAY CONSTRUCTION AS
 PER SECTION 1007 OF SBC 1997.
 -INDICATE FIREBLOCKING. SEC 2305 SBC/97
 -TREAD AND RISER RATIO DOESN'T COMPLY
 WITH SECTION 1007.3 SBC 1997.
 6-SPECIFY DRAFSTOPPING TYPE AND LOCATION
 AT SECOND FLOOR FRAMING PLAN. SECTION
 2305.2.2 SBC 1997.
 7-STORM PANELS:
 -INSTALLATION SCHEDULE IS INCORRECT.
 ANCHOR SPECIFIED IS FOR CONCRETE OR
 MASONRY INSTALLATION ONLY. WHAT ABOUT
 SECOND FLOOR WOOD FRAMED WALLS?
 REVISE TYPE AND SPACING OF ANCHOR AS
 REQUIRED.
 -PROVIDE AN UPDATED PRODUCT APPROVAL.
 8-PROVIDE SPECIFICATIONS/DETAILS FOR
 CEILING CONSTRUCTION AT ENTRY AND REAR
 PORCHES. SPECIFY ANCHOR TYPES AND
 SPACING. SECTION 2504 SBC 1997.
 9-PROVIDE PRODUCT APPROVALS FOR TWO HOUR
 FIRE RATED CONCRETE BLOCK, WINDOW
 MULLIONS, OVAL WINDOW, ROOF TILE AND
 SLIDING GLASS DOORS.