2001-01-08 00:00:00 | SECOND CHECKLIST: |
| 1-PERCENTAGE OF OPENINGS ALLOWED BY |
| TABLE 600 OF SBC 1997 ISEXCEEDED AT |
| RIGHT ELEVATION. DWGS WERE NOT REVISED |
| 2-DETAIL/SECTION AT COLUMN C8 IS |
| INCOMPLETE. IT DOESN'T SPECIFY BOTTOM |
| PLATE AND ANCHORS. |
| SECTION 104.2.2 CITY AMENDMENTS. |
| 3-PROVIDE A COMPLETE WALL SECTION AT TWO |
| STORY CBS WALL. INCLUDE DETAIL/SPECS |
| OF HOW IS SECOND FLOOR FRAMING |
| ANCHORED TO THIS WALL. SECTION 104.2.2 |
| CITY AMENDMENTS TO SBC 1997. |
| 4-PROVIDE SAFETY GLASS AT BEDROOM #4. |
| SECTION 2405.2 SBC 1997. |
| 5-STAIRS SECTION/DETAIL: |
| -NOT ENOUGH INFORMATION IS GIVEN TO |
| DETERMINE THE STAIRWAY CONSTRUCTION AS |
| PER SECTION 1007 OF SBC 1997. |
| -INDICATE FIREBLOCKING. SEC 2305 SBC/97 |
| -TREAD AND RISER RATIO DOESN'T COMPLY |
| WITH SECTION 1007.3 SBC 1997. |
| 6-SPECIFY DRAFSTOPPING TYPE AND LOCATION |
| AT SECOND FLOOR FRAMING PLAN. SECTION |
| 2305.2.2 SBC 1997. |
| 7-STORM PANELS: |
| -INSTALLATION SCHEDULE IS INCORRECT. |
| ANCHOR SPECIFIED IS FOR CONCRETE OR |
| MASONRY INSTALLATION ONLY. WHAT ABOUT |
| SECOND FLOOR WOOD FRAMED WALLS? |
| REVISE TYPE AND SPACING OF ANCHOR AS |
| REQUIRED. |
| -PROVIDE AN UPDATED PRODUCT APPROVAL. |
| 8-PROVIDE SPECIFICATIONS/DETAILS FOR |
| CEILING CONSTRUCTION AT ENTRY AND REAR |
| PORCHES. SPECIFY ANCHOR TYPES AND |
| SPACING. SECTION 2504 SBC 1997. |
| 9-PROVIDE PRODUCT APPROVALS FOR TWO HOUR |
| FIRE RATED CONCRETE BLOCK, WINDOW |
| MULLIONS, OVAL WINDOW, ROOF TILE AND |
| SLIDING GLASS DOORS. |