Plan Review Notes
Plan Review Notes For Permit 00050758
Permit Number 00050758
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLANS SUBMITTED ARE SHOWING
 ELECTRICAL HEATER? CONTRACT IS SHOWING
 GAS? WHICH IS IT?
  
 2)NOTE: IF ELECTRIC, NEED TO SUBMIT LOAD
 CALCULATIONS FOR EXISTING SERVICE AND
 LOAD BEING ADDED BY ELEC. HEATER.
 SHOW EXISTING SERVICE SIZE.215-5
  
  
 3)NOTE: ALSO, YOU ARE SHOWING 3#12`S
 GOING TO POOL HEATER? PLEASE SHOWTHE
 CORRECT WIRING METHOD.215-5
  
 PLEASE SUBMIT ALL THE ABOVE INFORAMTION
 FOR REVIEW. IF THERE AREANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372