2001-01-08 00:00:00 | ***************** UNSAT **************** |
| |
| 1)NOTE: PLEASE SUBMIT THE AIC RATING OF |
| EQUIPMENT MAIN. MAINS MUST BE RATED FOR |
| THE AVAILABLE FAULT CURRENT.110-9/215-5 |
| THIS IS REQ`D ON ALL PLANS. |
| |
| 2)NOTE: PLEASE INCLUDE THE COLD WATER |
| PIPE AND BLDG.STEEL AS PART OF THE |
| GROUNDING ELETRODE SYSTEM,AS PER 250-50 |
| |
| 3)NOTE: PLEASE INDICATE THE PANEL AS \\ |
| BEING MAIN BRKR 215-5 |
| |
| 4)NOTE: PLEASE SHOW THE REQ`D DEDICATED |
| BATH(S) CIRCUIT(S) PER 210-11-C-3 |
| |
| 5)NOTE: PLEASE SEE THE MISSING OUTLET |
| REQ`D FOR TWO FEET OF WALL 210-52. |
| |
| 6)NOTE: PLEASE NOTE THAT SMOKE DETECTORS |
| ARE REQ`DOUTSIDE ALL SLEEPING ROOMS |
| IN NEW DWELLINGS. NFPA-72 2-2.1.1.1 |
| |
| 7)NOTE:PLEASE COMPLETE LOAD CALCULATION. |
| |
| 8)NOTE:PLEASE SEE PANEL SCHEDULE.YOU |
| SHOW 4500VAON 20AMPTHIS MUST BE |
| RATED AT 125% OF MIN CIRCUIT AMPACITY, |
| |
| |
| 9)NOTE: PLEASE SHOW THE SWITCH LOCATION |
| FOR EGRESS LIGHTING IN GARAGE. |
| |
| PLEASE SUBMIT ALL THE ABOVE INFORMATION |