Plan Review Notes
Plan Review Notes For Permit 00050266
Permit Number 00050266
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT THE AIC RATING OF
 EQUIPMENT MAIN. MAINS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT.110-9/215-5
 THIS IS REQ`D ON ALL PLANS.
  
 2)NOTE: PLEASE INCLUDE THE COLD WATER
 PIPE AND BLDG.STEEL AS PART OF THE
 GROUNDING ELETRODE SYSTEM,AS PER 250-50
  
 3)NOTE: PLEASE INDICATE THE PANEL AS \\
 BEING MAIN BRKR 215-5
  
 4)NOTE: PLEASE SHOW THE REQ`D DEDICATED
 BATH(S) CIRCUIT(S) PER 210-11-C-3
  
 5)NOTE: PLEASE SEE THE MISSING OUTLET
 REQ`D FOR TWO FEET OF WALL 210-52.
  
 6)NOTE: PLEASE NOTE THAT SMOKE DETECTORS
 ARE REQ`DOUTSIDE ALL SLEEPING ROOMS
 IN NEW DWELLINGS. NFPA-72 2-2.1.1.1
  
 7)NOTE:PLEASE COMPLETE LOAD CALCULATION.
  
 8)NOTE:PLEASE SEE PANEL SCHEDULE.YOU
 SHOW 4500VAON 20AMPTHIS MUST BE
 RATED AT 125% OF MIN CIRCUIT AMPACITY,
  
  
 9)NOTE: PLEASE SHOW THE SWITCH LOCATION
 FOR EGRESS LIGHTING IN GARAGE.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 659-8096 EXT 8372