2001-01-08 00:00:00 | 1)INDICATE TYPE OF PIPING FOR GAS SYSTEM |
| TO ENSURE COMPLIANCE W/SGC.(JOB SPECS. |
| ARE NOT WITH PLANS.) |
| |
| 2)SHT.A2.0-RESTROOM FIXTURE CALCULATIONS |
| ARE NOT IN COMPLIANCE W/SPC TABLE 407 |
| FOR THE TYPE OF OCCUPANCIES AND OCCUPANT |
| LOAD.RESTAURANT LOAD TO BE BASED ON |
| NUMBER OF SEATS NOTED ON SHEET A5.1. |
| (154)AN ADDITIONAL WATER CLOSET IS REQD. |
| IN EACH TOILET ROOM. |
| |
| 3)ADDITIONAL INFORMATION REQD.FOR POWER |
| VENT FOR GAS WATER HEATER.SEE SHT.M1, |
| NOTE #4. |
| |
| 4)SHT.M1-SUBMITTED COMBUSTION AIR CALC- |
| ULATIONS ARE DEFICIENT AS DESIGNED. |
| COMPLY W/SGC SEC.402.4.4.4(3),NFPA 5.3.5 |
| |
| 5)SHT.M2-KIT.EQUIP.#P-11A SHALL |
| DISCHARGE TO GREASY WASTE.SPC 1004.4. |
| |
| 6)DISHWASHER SHALL DISCHARGE TO THE |
| SANITARY SYSTEM PER CITY OF WPB ORDIN- |
| ANCE. |
| |
| 7)COMBINATION WASTE AND VENT SYSTEM IS |
| NOT SIZED TO SPC SEC.921.4.1-921.4.2. |
| SYSTEM SHALL DISCHARGE TO THE GREASY |
| WASTE SYSTEM,NOT THE SANITARY.SPC SEC. |
| 1004.4. |
| |
| 8)SUBMIT APPROVAL FORM FROM CITY OF WPB |
| UTILITIES DEPT.FOR GREASE TRAP.COUNTY |
| WIDE AMENDMENTS TO SPC SEC.101.4.7. |
| CONTACT R.COMPO AT 561-835-7423. |
| |
| 9)WATER SUPPLY CONTROL SHALL COMPLY W/ |
| SPC SEC.610.4.1.,610.4.2. |
| |
| 10)DISPOSAL OF CONDENSATE SHALL COMPLY |
| W/SMC SEC.304.8.3.(SEE SHT.M3,COL.A6) |
| |
| 11)DRESSING ROOM BENCH SHALL BE LOCATED |
| ALONG THE LONGER DIMENSION WALL PER |
| FACBC SEC.4.35.4. |
| |
| 12)URINALS SHALL BE SCREENED FOR PRIVACY |
| PER SPC SEC.404.3. |
| |
| 13)SEE ATTACHED DRAWING FOR GREASE TRAP. |
| |
| IF YOU HAVE ANY QUESTIONS I CAN BE |
| REACHED AT 561-659-8096,EXT.8377. |
| TIMOTHY LARGE,PLUMBING PLANS EXAMINER. |