Plan Review Notes
Plan Review Notes For Permit 00050057
Permit Number 00050057
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001)INDICATE TYPE OF PIPING FOR GAS SYSTEM
 TO ENSURE COMPLIANCE W/SGC.(JOB SPECS.
 ARE NOT WITH PLANS.)
  
 2)SHT.A2.0-RESTROOM FIXTURE CALCULATIONS
 ARE NOT IN COMPLIANCE W/SPC TABLE 407
 FOR THE TYPE OF OCCUPANCIES AND OCCUPANT
 LOAD.RESTAURANT LOAD TO BE BASED ON
 NUMBER OF SEATS NOTED ON SHEET A5.1.
 (154)AN ADDITIONAL WATER CLOSET IS REQD.
 IN EACH TOILET ROOM.
  
 3)ADDITIONAL INFORMATION REQD.FOR POWER
 VENT FOR GAS WATER HEATER.SEE SHT.M1,
 NOTE #4.
  
 4)SHT.M1-SUBMITTED COMBUSTION AIR CALC-
 ULATIONS ARE DEFICIENT AS DESIGNED.
 COMPLY W/SGC SEC.402.4.4.4(3),NFPA 5.3.5
  
 5)SHT.M2-KIT.EQUIP.#P-11A SHALL
 DISCHARGE TO GREASY WASTE.SPC 1004.4.
  
 6)DISHWASHER SHALL DISCHARGE TO THE
 SANITARY SYSTEM PER CITY OF WPB ORDIN-
 ANCE.
  
 7)COMBINATION WASTE AND VENT SYSTEM IS
 NOT SIZED TO SPC SEC.921.4.1-921.4.2.
 SYSTEM SHALL DISCHARGE TO THE GREASY
 WASTE SYSTEM,NOT THE SANITARY.SPC SEC.
 1004.4.
  
 8)SUBMIT APPROVAL FORM FROM CITY OF WPB
 UTILITIES DEPT.FOR GREASE TRAP.COUNTY
 WIDE AMENDMENTS TO SPC SEC.101.4.7.
 CONTACT R.COMPO AT 561-835-7423.
  
 9)WATER SUPPLY CONTROL SHALL COMPLY W/
 SPC SEC.610.4.1.,610.4.2.
  
 10)DISPOSAL OF CONDENSATE SHALL COMPLY
 W/SMC SEC.304.8.3.(SEE SHT.M3,COL.A6)
  
 11)DRESSING ROOM BENCH SHALL BE LOCATED
 ALONG THE LONGER DIMENSION WALL PER
 FACBC SEC.4.35.4.
  
 12)URINALS SHALL BE SCREENED FOR PRIVACY
 PER SPC SEC.404.3.
  
 13)SEE ATTACHED DRAWING FOR GREASE TRAP.
  
 IF YOU HAVE ANY QUESTIONS I CAN BE
 REACHED AT 561-659-8096,EXT.8377.
 TIMOTHY LARGE,PLUMBING PLANS EXAMINER.