Plan Review Notes For Permit 00050057 |
Permit Number |
00050057 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ************** UNSAT***************** | | | | 1)NOTE: UNSAT FOR PHASE TWO (II) | | PLEASE SEE AND ADDRESS FIRST SET OF | | NOTES GIVEN BY JAKE LEAHY. | | | | 2)NOTE: PLEASE PROVIDE CONDUIT LAYOUT | | PLAN, SHOWING CONDUIT SIZES FOR PHASE | | I ONLY. | | | | 3)NOTE: PLEASE SUBMIT SPECS ON 1400 AMP | | OCP SHOWN AT 1600AMP MAIN. 1400 AMP | | FUSES ARE NOT STANDARD AND IF YOU HAVE | | A MANUFACTURE`S LISTING, THEN PLEASE | | SUBMIT. SEE ART;240-6 | | | | | | IF WIRE SIZES, AND CONDUIT SIZES CHANGE | | DUE TO MAIN OCP THEN THERE WOULD BE A | | PROBLEM ISSUING ANY PERMIT FOR PHASE I | | ELECTRICAL. | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | FOR REVIEW. IF THERE ARE ANY QUESTIONS | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-659-8096 EXT 8372 |
|