Plan Review Notes
Plan Review Notes For Permit 00050057
Permit Number 00050057
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00************** UNSAT*****************
  
 1)NOTE: UNSAT FOR PHASE TWO (II)
 PLEASE SEE AND ADDRESS FIRST SET OF
 NOTES GIVEN BY JAKE LEAHY.
  
 2)NOTE: PLEASE PROVIDE CONDUIT LAYOUT
 PLAN, SHOWING CONDUIT SIZES FOR PHASE
 I ONLY.
  
 3)NOTE: PLEASE SUBMIT SPECS ON 1400 AMP
 OCP SHOWN AT 1600AMP MAIN. 1400 AMP
 FUSES ARE NOT STANDARD AND IF YOU HAVE
 A MANUFACTURE`S LISTING, THEN PLEASE
 SUBMIT. SEE ART;240-6
  
  
 IF WIRE SIZES, AND CONDUIT SIZES CHANGE
 DUE TO MAIN OCP THEN THERE WOULD BE A
 PROBLEM ISSUING ANY PERMIT FOR PHASE I
 ELECTRICAL.
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372