Plan Review Notes For Permit 00050015 |
Permit Number |
00050015 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | DENIED FOR MECHANICAL | | | | BASED ON PLAN REVIEW 00030112 THE FOLLOW | | ING ITEMS NEED TO BE REVISED ON THE MECH | | DRAWINGS: | | 1) PROVIDE INFORMATION ON BATH EXHAUST | | DUCT MATERIAL FOR CODE COMPLIANCE | | 2) OUTSIDE AIR CALCULATIONS LOCATED ON | | SKM-9 NEED TO BE PERMANTLY ATTACHED TO | | APPROVED DRAWINGS | | 3) AIR BALANCE SCHEDULE LOCATED ON SKM- | | 10 NEEDS TO BE PERMANENTLY ATTACHED TO | | APPROVED DRAWINGS | | 4) ALL FIRE DAMPER LOCATIONS TO BE SHOWN | | AND PROPERLY IDENTIFIED ON PLANS PER | | 1997 SMC 610.6 | | 5) FIRE DAMPERS REQUIRED AT ALL WALL | | PENETRATIONS OF 1 HOUR OR MORE PER 1997 | | SMC 610.1.2 SEE PRIOR LIST FOR SPECIFICS | | | | THE FOLLOWING ARE PROVISO ITEMS: | | 1) KITCHEN HOOD AND EXHAUST DUCT WILL | | REQUIRE SEPARATE MECHANICAL PERMIT | | 2) SEPARATE PERMITS REQUIRED FOR HOOD, | | SUPPRESSION, WALK IN COOLER/FREEZER,ETC. |
|