Plan Review Notes
Plan Review Notes For Permit 00041354
Permit Number 00041354
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: NEED TO SUBMIT THE AIC RATING
 OF EQUIPMENT MAINS AND PANELS.215-5
 MAINS MUST BE RATED FOR THE AVAILABLE
 FAULT CURRENT AS PER 110-9
  
 2)NOTE: NEED TO HAVE THE REQ`D DEDICATED
 BATH(S) CIRCUIT(S) TO BE 20 AMP AND #12
 AWG. AS PER 210-11-C-3
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS CALL
 659-8096 EXT 8372
  
  
 ***************NOTE*********************
  
 SHEET A-4(ELEC) MAY BE CHANGED OUT
 BY ARCH ENT. BEFORE BLDG.DOES THEIR PLAN
 REVIEW. THIS WAY MAYBE THE PLANS WON`T
 HAVE TO COME BACK JUST FOR ELEC. COMMENT
 -S.