2001-01-08 00:00:00PASSED WITH PROVISOS
 PROJECT RECIEVED FOR ENG REVIEW 6/1/00
  
 REVIEW COMMENTS FOR SHEET C-2
  
 1. DIRECT TAPS MUST BE CALLED OUT
 SPECIFIYING SIZE AND INSTALLATION BY
 CONTRACTOR. (NO SADDLE TAPS ALLOWED)
  
 2. REDUCE PREASSURE ASSEMBLIES MUST BE
 INSTALLED AS MARKED ON PLAN.
  
 3. BACKFLOWS MUST BE INSTALLED IN THE
 PROPERTY JUST INSIDE THE R.O.W. LINE.
  
 4. METERS MUST BE INSTALLED JUST OUSIDE
 OF THE R.O.W.
  
 5. VERTICAL CLEARANCES MUST BE CALLED
 OUT BETWEEN WATER AND SEWER. AN 18"
 MINIMUM CLEARANCE IS REQUIRED.
  
 6. MUST HAVE ON PLAN "SUNSHINE" LOCATING
 SERVICE NOTE ALONG WITH THE TELEPHONE
 NUMBER 1 800 432 4770.
  
 7. SUPPLY STANDARD UTILITY DETAIL
 DRAWINGS TO CONTRACTOR. THIS APPLY'S
 TO SERVICES, BACKFLOW, CLEAN-OUTS,
 AND LATERALS ETC.
  
 8. SUBMITSHOP DRAWINGS TO PROJECT
 COORDINATOR FOR WATER SERVICES AND STORM