Plan Review Notes For Permit 00040985 |
Permit Number |
00040985 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ***************PROVISO****************** | | WATER HEATER SHALL BE READILY ACCESSIBLE | | PER SPC SEC.501.7.SUPPLY FIXED LADDER | | FOR ACCESS OR RELOCATE EWH TO FLOOR. | | | | PROVISIONS SHALL BE MADE AT DRINKING | | FOUNTAIN FOR PEOPLE WHO HAVE TROUBLE | | BENDING OR STOOPING.FACBC SEC.4.1.3.(10) | | (A). | | | | SUBMIT MANUF.SHEETS FOR STEAMER UNITS. | | MAX.TEMPERATURE OF WASTE DISCHARGED TO | | SANITARY SHALL BE 140 DEGREES PER SPC | | SEC.717.8 | | | | FLOOR SINKS SHALL BE INSTALLED IN LIEU | | OF HUB DRAINS AND SHALL BE OF A DESIGN | | THAT PREVENTS SPLASHING PER SPC SEC. | | 807.1.3. | | | | SHOW LOCATION OF 2ND.DRINKING FOUNTAIN | | ON FLOOR PLAN.COUNTYWIDE AMENDMENTS TO | | SPC SEC.104.2.1. | | | | IF YOU HAVE ANY QUESTIONS I CAN BE | | REACHED AT 561-659-8096,EXT.8377. | | | | TIMOTHY LARGE,PLUMBING PLANS EXAMINER. |
|