Date Text
2001-01-08 00:00:00***************PROVISO******************
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7.SUPPLY FIXED LADDER
 FOR ACCESS OR RELOCATE EWH TO FLOOR.
  
 PROVISIONS SHALL BE MADE AT DRINKING
 FOUNTAIN FOR PEOPLE WHO HAVE TROUBLE
 BENDING OR STOOPING.FACBC SEC.4.1.3.(10)
 (A).
  
 SUBMIT MANUF.SHEETS FOR STEAMER UNITS.
 MAX.TEMPERATURE OF WASTE DISCHARGED TO
 SANITARY SHALL BE 140 DEGREES PER SPC
 SEC.717.8
  
 FLOOR SINKS SHALL BE INSTALLED IN LIEU
 OF HUB DRAINS AND SHALL BE OF A DESIGN
 THAT PREVENTS SPLASHING PER SPC SEC.
 807.1.3.
  
 SHOW LOCATION OF 2ND.DRINKING FOUNTAIN
 ON FLOOR PLAN.COUNTYWIDE AMENDMENTS TO
 SPC SEC.104.2.1.
  
 IF YOU HAVE ANY QUESTIONS I CAN BE
 REACHED AT 561-659-8096,EXT.8377.
  
 TIMOTHY LARGE,PLUMBING PLANS EXAMINER.