Plan Review Notes For Permit 00040985
Permit Number 00040985
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT SQ.FOOTAGE OF HABITABLE FLOOR
 SPACE TO ENSURE COMPLIANCE W/TABLE 407
 OF SPC 1994 EDITION.REFER TO SEC.407.1.3
 FOR ALLOWED DEDUCTIBLE AREAS.
  
 PLANS SHALL BEAR CITY PLACE LANDLORD
 APPROVAL STAMPS.
  
 SINK AT KITCHEN AREA SHALL COMPLY W/
 FACBC SECS.4.24.1-4.24.7.
  
 SANITARY FACILITIES AND DRINKING
 FOUNTAIN SHALL BE ACCESSIBLE TO THE
 PUBLIC PER SPC SEC.407.2.2.
  
 DRINKING FOUNTAIN SHALL COMPLY W/FACBC
 SEC.4.1.3.(10)(A),4.15.PROVISIONS SHALL
 BE MADE FOR PERSONS WHO HAVE TROUBLE
 BENDING OR STOOPING.SUBMIT DETAIL.
  
 SHOW DIMENSIONS OF TOILET ROOMS.SIZE AND
 CLEAR FLOOR SPACE FOR FIXTURES SHALL
 COMPLY W/FACBC SEC.4.16,FIG.28.
  
 SHT.A-17-LENGTH OF GRAB BARS BEHIND AND
 ALONG SIDE WATER CLOSETS SHALL COMPLY
 W/FACBC SECS.4.16.4,FIG.#29.
  
 HEIGHT OF TOWEL DISPENSERS SHALL COMPLY
 W/FACBC SEC.4.2.5, 4.2.6.
  
 SHOW HEIGHT OF H.C.WATER CLOSET.COMPLY
 W/FACBC SEC.4.16.3.
  
 CLEAR FLOOR SPACE UNDER H.C.LAV.SHALL
 COMPLY W/FACBC SEC.4.19.2.
  
 WATER HEATER SHALL BE READILY ACCESSIBLE
 PER SPC SEC.501.7.PROVIDE FIXED LADDER
 OR RELOCATE TO FLOOR.
  
 SUBMIT MANUF.SHEETS FOR STEAMERS.MAX.
 TEMP.OF WATER TO SANITARY SHALL BE 140
 DEGREES PER SPC SEC.717.8.