Plan Review Notes
Plan Review Notes For Permit 00040985
Permit Number 00040985
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************DENIED*********************
  
 1) EXHAUST FANS NOTE 2 SHOW VENT TO
 ABOVE CEILING SPACE. 1997 SMC 501.3
 REQUIRES ALL EXHAUST TO BE DISCHARGED
 OUTDOORS.
 2) SAFE ROOM SHOWS NO VENTILATION.
 1997 SMC 403 REQUIRES EVERY PORTION OF
 EVERY BUILDING TO BE VENTILATED IN
 ACCORDANCE WITH ASHRAE 62-89
 3) DIFFUSER DETAIL INDICATES FLEX
 ATTACHMENT METHOD. NOTE METHOD TO COMPLY
 WITH ENERGY EFFICIENCY CODE FOR BLDG
 CONSTRUCTION 1997 410.1ABCD.3.3