Plan Review Notes For Permit 00040985 |
Permit Number |
00040985 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | *************** PROVISO ************** | | | | 1)NOTE: PLEASE CORRECT THE EQUIPMENT | | GROUNDING CONDUCTOR YOU SHOW ON E-4. | | AS PER 250-122 OF THE '99' NEC 400 AMP | | OC PROTECTION REQ`S #3. | | | | 2)NOTE: ALSO FOR THE COLOR CODING ON E-5 | | YOU SHOW FOR 277/480 GRAY AND WHITE WITH | | STRIPE. UNDER THE LOCAL AMENDMENTS ART; | | 215, 277/480 REQ`S ONLY GRAY. | | PLEASE REMOVE THE WORDING FOR WHITE W/ | | STRIPE. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW BEFORE ANY ROUGH ELECTRICAL | | INSPECTION IS CALLED IN. IF THERE ARE | | ANY QUESTIONS PLEASE CALL (561)659-8096 | | EXT 8372 |
|