Plan Review Notes
Plan Review Notes For Permit 00040942
Permit Number 00040942
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00FLOOR DRAINS ARE REQD.IN THE COMMON
 LAUNDRY ROOMS PER SPC SEC.409.4.5.
  
 PLUMBING DRAWINGS SHOW A 2"PD LINE
 REDUCING TO 1 1/2".CLARIFY.
  
 SHT.DAPT-P5.01-TUBS LOCATED DOWNSTREAM
 OF WATER CLOSETS SHALL BE VENTED PER SPC
 913.2.
  
 ALL BATHROOMS IN THE DWELLING UNIT SHALL
 COMPLY W/THE PROVISIONS OF THE FEDERAL
 FAIR HOUSING ACT 24 CFR 100.205 (C)(3)
 (IV),REQ.#7(2),PARAGRAPH (A) OR (B).
 INDICATE ON THE PLANS WHICH DESIGN
 OPTION (A OR B) IS BEING USED.
  
 COMMON AREA LAUNDRY ROOMS SHALL COMPLY
 W/FEDERAL FAIR HOUSING ACT REQ.#3(USABLE
 DOORS),AND ANSI SEC.4.32.6.
  
 CLEAR SPACE OF 30"WIDE SHALL BE PROVIDED
 BETWEEN FRONT OF TOILET BOWL AND WALL
 TO PROVIDE PERPENDICULAR APPROACH TO TUB
 IF FHA DESIGN OPTION "A"IS USED.
  
 DOORS IN BATHROOMS SHALL NOT SWING INTO
 CLEAR FLOOR SPACE REQD.FOR ANY FIXTURE.
 SHOW CLEAR FLOOR SPACES ON PLANS AND
 COMPLY W/REQS.OF FEDERAL FAIR HOUSING
 ACT 24 CFR 100.205.
  
 SHT.DAPT-A7.05-MAX.DISTANCE TO BOTTOM OF
 WOOD BLOCKING ABOVE LIP OF TUB SHALL BE
 6" PER FHA REQ.#6,FIGURE #4.