Date |
Text |
2001-01-08 00:00:00 | FLOOR DRAINS ARE REQD.IN THE COMMON |
| LAUNDRY ROOMS PER SPC SEC.409.4.5. |
| |
| PLUMBING DRAWINGS SHOW A 2"PD LINE |
| REDUCING TO 1 1/2".CLARIFY. |
| |
| SHT.DAPT-P5.01-TUBS LOCATED DOWNSTREAM |
| OF WATER CLOSETS SHALL BE VENTED PER SPC |
| 913.2. |
| |
| ALL BATHROOMS IN THE DWELLING UNIT SHALL |
| COMPLY W/THE PROVISIONS OF THE FEDERAL |
| FAIR HOUSING ACT 24 CFR 100.205 (C)(3) |
| (IV),REQ.#7(2),PARAGRAPH (A) OR (B). |
| INDICATE ON THE PLANS WHICH DESIGN |
| OPTION (A OR B) IS BEING USED. |
| |
| COMMON AREA LAUNDRY ROOMS SHALL COMPLY |
| W/FEDERAL FAIR HOUSING ACT REQ.#3(USABLE |
| DOORS),AND ANSI SEC.4.32.6. |
| |
| CLEAR SPACE OF 30"WIDE SHALL BE PROVIDED |
| BETWEEN FRONT OF TOILET BOWL AND WALL |
| TO PROVIDE PERPENDICULAR APPROACH TO TUB |
| IF FHA DESIGN OPTION "A"IS USED. |
| |
| DOORS IN BATHROOMS SHALL NOT SWING INTO |
| CLEAR FLOOR SPACE REQD.FOR ANY FIXTURE. |
| SHOW CLEAR FLOOR SPACES ON PLANS AND |
| COMPLY W/REQS.OF FEDERAL FAIR HOUSING |
| ACT 24 CFR 100.205. |
| |
| SHT.DAPT-A7.05-MAX.DISTANCE TO BOTTOM OF |
| WOOD BLOCKING ABOVE LIP OF TUB SHALL BE |
| 6" PER FHA REQ.#6,FIGURE #4. |