2001-01-08 00:00:00PROVISO:
  
 1) AC-7 AND AC-6 UNITS SERVING CORRIDORS
 TO HAVE FAN SHUT DOWN BY DUCT SMOKE
 DETECTORS PER 1997 SMC 406.2RECIRCULA-
 TING FANS SERVING AREAS USED FOR EGRESS
 2) OVERFLOW PROTECTION REQUIRED FOR
 ALL A/C UNITS
 3) RISERS WHICH ARE SUBJECT TO MOISTURE
 SHALL BE LINED WITH SUITABLE MATERIAL
 TO PREVENT DETERIORATION OF DRYWALL
 ENCLOSURE PER LOCAL AMENDMENTS 610.1.3.2