1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ENERGY FORM NEEDS THE CORRECT ADDRESS | | AND PERMIT NUMBER FILLED IN. | | | | | | | | THE DESIGN COMPLIANCE FORM NEEDS THE | | ADDRESS FILLED IN BY THE DESIGNER OF | | RECORD. | | | | PLAN #1 STATES TWO DIFFERENT WIND | | PRESSURES FOR THE OPENINGS.CLARIFY | | | | PROVIDE A CLEAR LEGIABLE COPY OF THE | | SINGL HUNG WINDOW PRODUCT APPROVAL. | | | | PLAN #2, GENERAL NOTES NUMBER 8 REFERS | | TO THE INCORRECT BUILDING CODE EDITION. | | | | PROVIDE SHOP DRAWINGS FOR THE PRECAST | | LENTELS. |
|