2001-01-08 00:00:00 | APPROVED WITH PROVISO: |
| 1-PROVIDE CURRENT PRODUCT APPROVAL FOR |
| MASONRY. |
| 2-MULLION PRODUCT APPROVAL IS TO BE USED |
| WITH SERIES 7500 SINGLE HUNG WINDOWS |
| MULLED TOGETHER ONLY. PROVIDE MULLION |
| PRODUCT APPROVAL FOR HORIZONTAL |
| APPLICATIONS. |
| -CLEARLY INDICATE MULLION SIZES AND |
| FASTENERS TO BE USED IN THIS PROJECT. |
| -PROVIDE UPDATED PRODUCT APPROVAL. |
| 3-PROVIDE PRODUCT APPROVAL FOR SLIDING |
| GLASS DOORS WITH TRANSOM ABOVE AS A |
| SINGLE ASSEMBLY AS SHOWN ON ARCHITECTS |
| DRAWINGS. |
| 4-PROVIDE STORM PANELS PRODUCT APPROVAL. |
| -HIGHLIGHT SPECIFIC MOUNTING CONDITIONS |
| AND ANCHOR TYPE AND SPACING TO BE USED |
| ACCORDING TO THE DESIGN PRESSURES |
| (MEAN ROOF HEIGHT), EDGE DISTANCE, |
| PANEL SPAN AND STRUCTURE TO BE |
| ANCHORED TO. |
| 5-UPDATE/REVISE ALL DRAWINGS AS REQUIRED |
| SEE COMMENTS ON PLANS. |
| 6-PROVIDE COMPLETE FRAMING DETAILS AT |
| ARCHED OPENINGS. SECTION 104.2.2 OF |
| CITY AMENDMENTS. |
| 7-PROVIDE SOIL TEST REPORT WITH THE |
| MINIMUM INFORMATION AS REQUESTED IN |
| SECTION 1804.2.7.2 CITY AMENDMENTS. |
| 8-ATTIC ACCESS TO BE 22"X36" MINIMUM. |
| SECTION 2309.6 SBC 1997.REVISE NOTE #7 |