2001-01-08 00:00:00 | APPROVED WITH PROVISO: |
| 1-PROVIDE CURRENT PRODUCT APPROVAL FOR |
| MASONRY. |
| 2-MULLION PRODUCT APPROVAL IS TO BE USED |
| WITH SERIES 7500 WINDOWS MULLED |
| TOGETHER ONLY. PROVIDE MULLION PRODUCT |
| APPROVAL FOR HORIZONTAL APPLICATIONS. |
| -CLEARLY INDICATE MULLION SIZES AND |
| FASTENERS TO BE USED IN THIS PROJECT. |
| -PROVIDE UPDATED PRODUCT APPROVAL. |
| 3-PROVIDE PRODUCT APPROVAL FOR SLIDING |
| GLASS DOORS WITH TRANSOM ABOVE AS A |
| SINGLE ASSEMBLY AS SHOWN ON ARCHITECTS |
| DRAWINGS. |
| 4-PROVIDE STORM PANELS PRODUCT APPROVAL. |
| -HIGHLIGHT SPECIFIC MOUNTING CONDITIONS |
| AND ANCHOR TYPE AND SPACING TO BE USED |
| ACCORDING TO THE DESIGN PRESSURES |
| (MEAN ROOF HEIGHT), EDGE DISTANCE, |
| PANEL SPAN AND STRUCTURE TO BE BE |
| ANCHORED TO. |
| 5-UPDATE/REVISE ALL DRAWINGS AS REQUIRED |
| SEE COMMENTS ON DRAWINGS. |
| 6-PROVIDE COMPLETE FRAMING DETAILS AT |
| ARCHED OPENINGS. SPECIFY FASTENERS AND |
| SPACING. SEC. 104.2.2 CITY AMENDMENTS. |
| 7-PROVIDE COPIES OF CURRENT PRODUCT |
| APPROVAL FOR "LA PORTE" FRENCH DOORS |
| WITH SIGNATURE OF PRODUCT CONTROL |
| EXAMINER. |
| 8-PROVIDE SOIL TEST REPORT WITH THE |
| MINIMUM INFORMATION AS REQUESTED IN |
| SECTION 1804.2.7.2 CITY AMENDMENTS. |
| 9-CLEARLY INDICATE ON PLANS AREAS TO |
| HAVE SAFETY GLASS. SEC. 2405.2 SBC/97. |
| SEE PLANS FOR COMMENTS. |
| 10-ENERGY CALCULATIONS: |
| -REVISE CEILING AREA CALCULATIONS. SEE |
| SECTION 604.1.A.1 FLORIDA ENERGY |
| EFFICIENCY CODE FOR BUILDING CONST'N |
| 1997 EDITION. |