Plan Review Notes
Plan Review Notes For Permit 00031741
Permit Number 00031741
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*************** UNSAT ******************
  
 1)NOTE: YOU SHOW THE SMOKE DETECTORS ON
 THE SAME CIRCUIT WITH THE BATH GFI`S.
 THIS IS NOT PERMITTED. 210-11-C-3
 BATH(S) ARE DEDICATED.
  
 2)NOTE: ALSO MISSING SMOKE DETECTOR
 OUTSIDE BEDROOM. IF THE DEN/BEDROOM IS
 GIVEN AS OPTIONAL BEDROOM THEN SD`S ARE
 REQ`D INSIDE AND OUTSIDE.
  
  
 3)NOTE:PANEL SCHEDULE SHOWS TWO SM APP-
 -LIANCE CIRCUITS.THIS DOES NOT CORRELATE
 WITH PLANS? THE LIGHTING IS SHOWN AS
 ONE OF THE CIRCUITS?? PLEASE CORRECT.
  
 4)NOTE: THE NOTESON THE LEFTHAND SIDE
 OF THE PLANS REFERENCE CODES FROM THE
 '96' NEC. PLEASE CORRECT CODE #`S TO
 REFLECT '99' NEC.
  
 5)NOTE:PLEASE SUBMIT AND HAVE DRAWN ON
 MAIN/PANEL THE AIC RATING OF THE MAIN
 BREAKER. MAIN MUST BE RATED FOR THE
 AVAILABLE FAULT CURRENT PER 110-9/215-5
 AIC RATINGS ARE FIGURED FROM FAULT
 CURRENT CALCULATIONS.
  
  
 PLEASE CORRECT AND SUBMIT ALL THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE ANY
 QUESTIONS PLEASE CALL 659-8096 EXT 8372