Plan Review Notes
Plan Review Notes For Permit 00031651
Permit Number 00031651
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-FLOOD ZONE "AO". NEED ELEVATION
 CERTIFICATE.
 -NOTE: LOWEST FLOOR ELEVATION TO BE NO
 LESS THAN 18" ABOVE THE CROWN OF THE
 ROAD. SEC 3107.1.1 CITY AMENDMENTS.
 2-CLEARLY INDICATE AREAS TO HAVE SAFETY
 GLASS. SEE PLANS FOR COMMENTS.
 SECTION 2405.2 SBC 1997.
 3-CLARIFY WINDOW SIZE FOR BEDROOMS #2
 AND #3. WHAT IS A SH 34+4?. WINDOW TO
 HAVE OPENING WITH A CLEAR HEIGHT OF
 24" MINIMUM. SEC 1005.4 SBC 1997.
 4-DESIGN CERTIFICATION FOR BUILDING CODE
 COMPLIANCE FORM:
 -ENGINEER WHO SEALED THIS FORM TO SEAL
 STRUCTURAL DRAWINGS TOO.
 -REVISE MEAN ROOF HEIGHT. 16'-0" PLUS
 OR MINUS. MEAN ROOF HEIGHT IS TAKEN
 FROM GRADE, NOT FROM FINISH FLOOR TO
 THE AVERAGE POINT OF THE HIGHEST ROOF.
 5-REVISE/UPDATE DRAWINGS. SEE COMMENTS
 ON PLANS.
 6-SOIL TEST REPORT TO HAVE ORIGINAL
 SIGNATURE AND DATE WHEN DOCUMENT WAS
 SEALED.
 7-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOOR WITHOUT SIDELITES AND WITH
 LEGIBLE DRAWINGS.
 8-PROVIDE COPIES OF TEST REPORTS FOR
 SLIDING GLASS DOORS AS PER ASTM E-330.
 SECTION 1706 SBC 1997.
 -PROFESSIONAL OF RECORD TO WRITE JOB
 LOCATION FOR SITE SPECIFIC PRODUCT
 APPROVAL FOR DOORS AND WINDOWS BY
 NORANDEX. ALSO CLEARLY INDICATE WHICH
 WINDOWS SIZES AND TYPES ARE GOING TO
 BE USED ON THIS PROJECT.
 -PROFESSIOANL OF RECORD TO CLEARLY
 PROVIDE NAME, ADDRESS, LICENSE NUMBER
 AND TELEPHONE ON THIS DOCUMENT ALSO.
 9-STORM PANELS:
 -CLEARLY INDICATE FASTENING METHOD TO
 BE USED AND HIGHLIGHT ANCHOR TYPE AND
 SPACING ACCORDING TO THE DESIGN
 PRESSURES, STORM PANEL SPAN, EDGE
 DISTANCE AND BUILDING STRUCTURE (THIS
 IS MASONRY CONSTRUCTION).