2001-01-08 00:00:00SUBMITTALS CHECKLIST:
 1-GARAGE DOOR PRODUCT APPROVAL DOESN'T
 MEET THE DESIGN PRESSURES CALCULATED
 BY THE ARCHITECT/ENGINEER OF RECORD.
 SEE ARCHITECTURAL PLANS.
 2-PRODUCT APPROVAL FOR SLIDING GLASS
 DOORS IS EXPIRED.
 -DRAWINGS ARE NOT LEGIBLE.
 -CLARIFY ARCHITECTURAL DRAWINGS. FLOOR
 PLAN SHOWS SLIDING GLASS DOORS WITH
 2 PANELS, WHILE, REAR ELEVATION SHOWS
 SLIDING GLASS DOORS WITH FOUR PANELS.
 REVISE DRAWINGS AS REQUIRED.
 3-PROVIDE PRODUCT APPROVAL FOR GLASS
 BLOCK. INFORMATION SUBMITTED IS PART
 OF MANUFACTURER'S SPECS BUT NOT THE
 ACTUAL PRODUCT APPROVAL.
 4-PROVIDE PRODUCT APPROVAL FOR ROUND
 WINDOW. PRODUCT APPROVAL SUBMITTED IS
 FOR HALF CIRCLE ONLY. SEE DRAWINGS.
 5-PROVIDE PRODUCT APPROVAL FOR SINGLE
 ENTRY DOOR AS SHOWN ON PLAN. PRODUCT
 APPROVAL SUBMITTED IS FOR SINGLE DOOR
 WITH SIDELITES ASSEMBLY.