Date |
Text |
2001-01-08 00:00:00 | APPROVED WITH PROVISO: |
| 1-ENERGY CALCULATIONS: |
| -REVISE NUMBER OF BEDROOMS. REVISE ALL |
| AREA CALCULATIONS AT ALL WALL TYPES |
| AND CEILING TYPES. SEE ARCHITECTURAL |
| PLANS AND SECTIONS 604 AND 605 OF FLA |
| ENERGY EFFICIENCY CODE FOR BUILDING |
| CONSTRUCTION, 1997 EDITION. |
| -COMPLETELY FILL INFORMATION ON TOP OF |
| ENERGY CALCULATIONS FORM. |
| 2-FLOOD ZONE "AO". WILL NEED TO PROVIDE |
| AN ELEVATION CERTIFICATE AFTER SLAB |
| IS POURED. |
| 3-MASTER BEDROOM TO HAVE A DOOR WITH 29" |
| MINIMUM CLEAR OPENING AS PER CHAPTER |
| 11 OF FLORIDA ACCESSIBILITY CODE FOR |
| BUILDING CONSTRUCTION, 1997 EDITION. |
| 4-PROVIDE COMPLETE SPECIFICATIONS FOR |
| CEILING CONSTRUCTION AT FRONT AND |
| BACK PORCHES. INCLUDING FASTENER TYPE |
| AND SPACING. SEC 2504 SBC 1997. |
| 5-STORM PANELS: |
| -PROVIDE A COMPLETE INSTALLATION SCHED. |
| AND KEY PLAN. CLEARLY SPECIFY MOUNTING |
| CONDITIONS AND ANCHORS TO BE USED |
| ACCORDING TO BUILDING CONSTRUCTION, |
| DESIGN PRESSURES, MEAN ROOF HEIGHT, |
| STORM PANEL SPAN AND EDGE DISTANCE. |
| 6-PROVIDE PRODUCT APPROVALS FOR: SINGLE |
| ENTRY DOOR, ROUND WINDOWS, WINDOW |
| MULLIONS, SLIDING GLASS DOORS, GLASS |
| BLOCK AND GARAGE DOOR. |
| 7-TRUSS DRAWINGS: |
| -MEAN ROOF HEIGHT IS 22'-6" PLUS OR |
| MINUS (MEAN ROOF HEIGHT IS TAKEN FROM |
| GRADE, NOT FROM FINISH FLOOR, TO THE |
| AVERAGE POINT OF THE HIGHEST ROOF. AND |
| THERE IS ONLY ONE MEAN ROOF HEIGHT FOR |
| ENTIRE BUILDING. TABLE 1606.2A SBC/97. |
| -CLARIFY WHY THE SIGNATURE ON TRUSS |
| LAYOUT IS DIFFERENT FROM THE ONE ON |
| ENGINEERED TRUSSES. ALSO, ENGINEER IS |
| TO SIGN AND DATE DOCUMENTS AT TIME OF |
| SEALING THEM. |