Plan Review Notes
Plan Review Notes For Permit 00031578
Permit Number 00031578
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-ENERGY CALCULATIONS:
 -REVISE NUMBER OF BEDROOMS. REVISE ALL
 AREA CALCULATIONS AT ALL WALL TYPES
 AND CEILING TYPES. SEE ARCHITECTURAL
 PLANS AND SECTIONS 604 AND 605 OF FLA
 ENERGY EFFICIENCY CODE FOR BUILDING
 CONSTRUCTION, 1997 EDITION.
 -COMPLETELY FILL INFORMATION ON TOP OF
 ENERGY CALCULATIONS FORM.
 2-FLOOD ZONE "AO". WILL NEED TO PROVIDE
 AN ELEVATION CERTIFICATE AFTER SLAB
 IS POURED.
 3-MASTER BEDROOM TO HAVE A DOOR WITH 29"
 MINIMUM CLEAR OPENING AS PER CHAPTER
 11 OF FLORIDA ACCESSIBILITY CODE FOR
 BUILDING CONSTRUCTION, 1997 EDITION.
 4-PROVIDE COMPLETE SPECIFICATIONS FOR
 CEILING CONSTRUCTION AT FRONT AND
 BACK PORCHES. INCLUDING FASTENER TYPE
 AND SPACING. SEC 2504 SBC 1997.
 5-STORM PANELS:
 -PROVIDE A COMPLETE INSTALLATION SCHED.
 AND KEY PLAN. CLEARLY SPECIFY MOUNTING
 CONDITIONS AND ANCHORS TO BE USED
 ACCORDING TO BUILDING CONSTRUCTION,
 DESIGN PRESSURES, MEAN ROOF HEIGHT,
 STORM PANEL SPAN AND EDGE DISTANCE.
 6-PROVIDE PRODUCT APPROVALS FOR: SINGLE
 ENTRY DOOR, ROUND WINDOWS, WINDOW
 MULLIONS, SLIDING GLASS DOORS, GLASS
 BLOCK AND GARAGE DOOR.
 7-TRUSS DRAWINGS:
 -MEAN ROOF HEIGHT IS 22'-6" PLUS OR
 MINUS (MEAN ROOF HEIGHT IS TAKEN FROM
 GRADE, NOT FROM FINISH FLOOR, TO THE
 AVERAGE POINT OF THE HIGHEST ROOF. AND
 THERE IS ONLY ONE MEAN ROOF HEIGHT FOR
 ENTIRE BUILDING. TABLE 1606.2A SBC/97.
 -CLARIFY WHY THE SIGNATURE ON TRUSS
 LAYOUT IS DIFFERENT FROM THE ONE ON
 ENGINEERED TRUSSES. ALSO, ENGINEER IS
 TO SIGN AND DATE DOCUMENTS AT TIME OF
 SEALING THEM.