Plan Review Notes For Permit 00031559 |
Permit Number |
00031559 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | CHECKLIST: | | 1-EGRESS WINDOWS IN BEDROOM #2 DON'T | | COMPLY WITH SECTION 1005.4 SBC 1997. | | 2-OPENINGS AT REAR ELEVATION EXCEED THE | | PERCENTAGE ALLOWED BY TABLE 600 SBC/97 | | CALCULATIONS SHOWN ON SHEET A-8 ARE | | MISSING THE SH H36 BY BREAKFAST AREA. | | ALSO, SEE WINDOWS AND DOORS PRODUCT | | APPROVAL FOR ACTUAL OPENING REQUIRED. | | THESE ARE THE RIGHT NUMBERS TO USE FOR | | OPENINGS CALCULATIONS. | | 3-UPDATE/REVISE ALL DRAWINGS AS REQUIRED | | SEE COMMENTS ON PLANS.USE SBC 97 NO 99 | | 4-ATTIC ACCESS TO BE 22"X36" MINIMUM. | | SECTION 2309.6 SBC 1997. | | 5-PRODUCT APPROVALS: | | -PROVIDE COPIES OF TEST RESULTS FOR | | SLIDING GLASS DOORS AS PER ASTM E 330 | | -DRAWINGS FOR OUTSWING ENTRY DOOR WITH | | LITES PRODUCT APPROVAL ARE NOT LEGIBLE | | 6-STORM PANELS: | | -REVISE KEY PLAN AND INSTALLATION SCHED | | TO MACTH ARCHITECT'S PLANS. SHEET A-8. | | NOTE: WAIT TILL ARCHITECT REVISES PLAN | | TO MEET THE TABLE 600 REQUIREMENTS. | | -USE MASONRY ANCHOR SPACING WHEN PANELS | | ARE TO BE ATTACHED TO MASONRY WITH | | FILLED CELLS. | | 7-FLOOD ZONE "AO". WILL NEED TO PROVIDE | | ELEVATION CERTIFICATE. | | 8-OWES $1235.01 FOR BUILDING VALUATION | | AND RADON FEES. |
|