Plan Review Notes
Plan Review Notes For Permit 00031559
Permit Number 00031559
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00CHECKLIST:
 1-EGRESS WINDOWS IN BEDROOM #2 DON'T
 COMPLY WITH SECTION 1005.4 SBC 1997.
 2-OPENINGS AT REAR ELEVATION EXCEED THE
 PERCENTAGE ALLOWED BY TABLE 600 SBC/97
 CALCULATIONS SHOWN ON SHEET A-8 ARE
 MISSING THE SH H36 BY BREAKFAST AREA.
 ALSO, SEE WINDOWS AND DOORS PRODUCT
 APPROVAL FOR ACTUAL OPENING REQUIRED.
 THESE ARE THE RIGHT NUMBERS TO USE FOR
 OPENINGS CALCULATIONS.
 3-UPDATE/REVISE ALL DRAWINGS AS REQUIRED
 SEE COMMENTS ON PLANS.USE SBC 97 NO 99
 4-ATTIC ACCESS TO BE 22"X36" MINIMUM.
 SECTION 2309.6 SBC 1997.
 5-PRODUCT APPROVALS:
 -PROVIDE COPIES OF TEST RESULTS FOR
 SLIDING GLASS DOORS AS PER ASTM E 330
 -DRAWINGS FOR OUTSWING ENTRY DOOR WITH
 LITES PRODUCT APPROVAL ARE NOT LEGIBLE
 6-STORM PANELS:
 -REVISE KEY PLAN AND INSTALLATION SCHED
 TO MACTH ARCHITECT'S PLANS. SHEET A-8.
 NOTE: WAIT TILL ARCHITECT REVISES PLAN
 TO MEET THE TABLE 600 REQUIREMENTS.
 -USE MASONRY ANCHOR SPACING WHEN PANELS
 ARE TO BE ATTACHED TO MASONRY WITH
 FILLED CELLS.
 7-FLOOD ZONE "AO". WILL NEED TO PROVIDE
 ELEVATION CERTIFICATE.
 8-OWES $1235.01 FOR BUILDING VALUATION
 AND RADON FEES.